24V 20KA 35mm Din rail signal surge protective devices
Lightning arrester for protecting measuring and controlling system
Product Description:
For installation at LPZ 0B-2 or higher, protecting for three unearthed single lines with direct or indirect to shield earth. Applied in measuring and controlling system, providing coarse and fine protection. Designed according to IEC 61643-21; GB 18802.21; YD/T 1542.
Main character:
1. Small size, only 7mm wide module
2. Connected to earth by DIN rail or earthing terminal.
3. With shield terminal (direct or indirect to earth)
Parameters:
Type |
|
BS RK 24 ST-DI |
Art.-No. | 610 502 | |
Norminal voltage | UN | 24V- |
Rated voltage (max. continuous d.c voltage) | Uc | 6V (Line-line), 60V (Line-PG), 30V (Line-shield), 160V (Shield-PG) |
Rated voltage (max. continuous a.c voltage) | Uc | 4.2V |
Nominal current | IL | 1A |
Lightning impulse current (10/350) | Iimp | 1kA |
Nominal discharge current (8/20) | In | 10kA |
Max.discharge current (8/20) | Imax | 20kA |
Voltage protection level for Iimp at 4kV (1.2/50us) | Up | ≤60V (Line-line), ≤60V (Line-PG), ≤60V (Line-shield) |
Max. load current |
IN |
250mA |
Series impedance per line | R | 4.7Ω |
Response time | tA | ≤4ns (Line-line), ≤20ns (Line-PG),≤20ns (Line-shield), ≤20ns (Shield-PG) |
Operating temperature range |
-40℃-+80℃ |
|
Cross-sectional area |
Max. 2.5mm2 flexible |
|
Mounting on |
35mm DIN rail. |
|
Enclosure material | orange thermoplastic, UL94-V0 | |
Test standards | YD/T 1542; GB 18802.21; IEC 61643-21 | |
Certification |
CE (LVD, EMC) |