XHHV High voltage impulse generator is mainly used for 32 kv and lower voltage cable fault impact discharging testing, also be used for DC withstand voltage testing of other electrical equipment. The power equipment integrated with the DC High voltage power source, energy-saving capacitor, discharging sphere interval into one body. The machine adopts Ergonomic design of operating mode, safe and reliable.
The machine has three voltage 8kv,16kv,32kv. The user can select a voltage according to the test situation. It is more convenient for different kind of cable fault testing. The machine also has the function of auto discharging and manual discharging,which provide more selection for user.
The XHHV Series surge generator provide strong power for pinpointing locating when use our model XHDD503/XHDD503A. which can locate the fault point accurately and quickly.
High voltage pulse output is even and controllable.
With current and voltage 1.5 pointer display and the surge discharge process is intuitive and clear.
High voltage side measurement is real-time and accurate.
With zero start protection function, and potentiometer return to Zero output function, safe and reliable.
Three voltage range and capacitors, which is easy to change the voltage as customer’s requirement.
This unique design of high voltage measurement, at stop state, it will auto discharge the capacitor electricity.
Discharge time with 2 modes: Timing and manual.
With DC Withstand voltage test function.
Internal installation high precision test cable fault sampling waveform module.
Humanized design trolley device, easy to move.
The surge HV voltage |
0 ~32kv |
High voltage divider | Voltage Accuracy 1.5 grade |
Inside capacitor |
4μF/32kV,16μF/16kV,64μF/8kV |
Surge time: | Auto surge about 4s, also can control by hands. |
Surge energy | 2048J |
Surge power |
2KVA |
Size | 534L×444W×805H |
Weight | not more than 75kg |
Power supply | AC 220V + 10% 50Hz/±2Hz |
Environment temperature |
-20 ~ +50 ℃ |