Description
11kV Isolators (Disconnectors) for use on line disconnection, isolation of substation apparatus and sectionalizing purposes.
The specification is for the following manually operated isolators:
***Overhead Line Isolator (Disconnector)
Applicable standards
IEC 62271-102, ISO 1461, IEC 60694
Service (indoor/outdoor)
The isolator will be suitable for continuous operation outdoors in tropical areas at altitudes of up to 2200m above sea level,
humidity of up to 90%, average ambient temperature of +30°C with a minimum of-1°C and a maximum of +40°C and heavy
saline conditions along the coast.
Model: GW-11/400-16
Type: Three phase operation, each switch pole incorporates three insulators mounted on hot dipped galvanized steel
underbase. The centre insulator is moveable to effect contact operation.
Operating mechanism: The isolator will be supplied complete with manual operating by means of push-pull reciprocating
mechanism. The mechanism is interlocked for safe operation.
Ratings | ||
Nominal System Voltage and frequency
|
11KV, 50HZ | |
Highest System Voltage of equipment
|
12KV | |
Rated continuous current
|
400A | |
Rated short time withstand current for 3s
|
16KA | |
Rated short circuit making current
|
16KA | |
Max temperature rise under rated voltage and current
|
60℃ | |
Creepage distance of insulator
|
300mm | |
Minimum clearance between phases (phase centres)
|
675mm | |
Minimum clearance to earth | 290mm | |
Mechanical endurance
|
5000 times
|
|
One minute power frequency withstand
voltage, wet,50Hz, 60s
|
With contacts closed | 38kV |
Across open contacts | 30KV | |
Lightning impulse withstand voltage,
1.2/50us, dry, +ve
|
With contacts closed
|
95kV
|
Across open contacts | 85KV |