They order glycol chiller from us working for brewing equipment since 2015;
Because the nice using feeling and recognize our chiller quality we always keep nice relationship for business.
Main Components List | ||||||
Item | Brand | Type | Original | |||
Compressor | HANBELL / BITZER | Semi-hermetic screw | Taiwan / Germany | |||
Pump | CNP | Inline pump | China | |||
Evaporator | MGREENBELT | Shell and tube | China | |||
Condenser | MGREENBELT | Shell and tube | China | |||
Thermal expansion valve | DANFOSS / ERMENSON | Denmark / USA | ||||
Drier Filter | DANFOSS / ERMENSON | Denmark / USA | ||||
Solenoid valve | DANFOSS | Denmark | ||||
Electric Components | SCHNEIDER | France |
Model | Terms | MG-600WSDL | MG-650WSDL | MG-700WSDL | MG-770WSDL | |||||
Cooling Capacity | 0 deg C outlet (kw) | 452 | 500 | 540 | 590 | |||||
-5 deg C outlet (kw) | 480 | 456 | 488 | 532 | ||||||
-10 deg C outlet (kw) | 340 | 380 | 406 | 444 | ||||||
Power Supply | 3 PHASE -380V-50Hz, or as customer local need | |||||||||
Refrigerant | Type | R22, R407C, R404A, R134A | ||||||||
Control | Thermostatic expansion valve | |||||||||
Compressor | Type | Semi-hermetic screw type | ||||||||
Circuit System | 2 | 2 | 2 | 2 | ||||||
Power (Kw) | 128 | 138 | 150 | 166 | ||||||
Capacity control | 25%~50%~75%~100% | |||||||||
Evaporator | Type | Shell and tube | ||||||||
Water flow 0 deg C | 77.5 m3/h | 85.7 m3/h | 92.6 m3/h | 101.1 m3/h | ||||||
Water flow -5 deg C | 82.3 m3/h | 78.2 m3/h | 83.7 m3/h | 91.2 m3/h | ||||||
Water flow -10 deg C | 58.3 m3/h | 65.1 m3/h | 69.6 m3/h | 76.1 m3/h | ||||||
Inlet / Outlet Pipe | DN 150 | DN 150 | DN 150 | DN 150 | ||||||
Condenser | Type | High efficiency threaded copper shell and tube | ||||||||
Cooling water flow | 109.4m3/h | 120.3 m3/h | 130.1m3/h | 142.6m3/h | ||||||
Inlet / Outlet Pipe | DN100*2 | DN125*2 | DN 125*2 | DN 125*2 | ||||||
Protect system | High and low pressure protection; overload protection; anti-phase protection, compressor over temperature protection;high pressure safety valve protection; oil pressure protection; exhaust over heat protection. | |||||||||
Dimension | cm | 400*120*200 | 400*120*200 | 440*120*200 | 440*120*220 | |||||
Weight | kg | 2150 | 2500 | 2700 | 3000 | |||||
Testing working condition: refrigerating medium inlet / outlet temperature 0 deg C / 5 deg C , Cooling water inlet / outlet temperature 30 deg C / 35 deg C. Customize accept for the special working need; Any specification will be changed based on technical update. |