100KV Automatic Portable Transformer Oil Breakdown Voltage Tester Sets
IIJ-II transformer oil tester fully automatic oil tester is apply to test the insulating oil's dielectric strength, which is designed as per the requirement of IEC156 Testing Method of Insulation Oil Medium Strength, which via proper programming, has got functions of auto boosting, step down, stirring, display and print out. After breakdown of oil medium, HV break off will operate within 10 seconds to enable an auto isolation of control system partly; this effectively safeguards the personnel security and equipment safety.
Application:
IIJ-II series fully automatic oil tester is apply to test the insulating oil's dielectric strength, which is designed as per the requirement of IEC165 Testing Method of Insulation Oil Medium Strength, which via proper programming, has got functions of auto boosting, step down, stirring, display and print out. After breakdown of oil medium, HV break off will operate within 10 seconds to enable an auto isolation of control system partly; this effectively safeguards the personnel security and equipment safety.
Features:
1. Simply operate: automatically (can be finished just press on key)
2. Menu controlled. Input data can clear
3. Can store 99 groups’ oil testing data which is convenient to reading and print. The testing data can keep 100 years under the condition of power off.
4. System time can go on running under power off; (The system time just for reference can not be the standard of timing).
5. Can upgrade software through RS232.
6. High capacity of anti-jamming and high precision of testing.
7. Small volume, light which operated in the open air very conveniently.
Advantages:
The automatic oil tester adopt industrial SCM to control which is applied to integrate circuit, new model I/0 connection, particular testing and anti-jamming technology which is largely improved the machine's capacity .
Technical Parameters:
Power supply: |
AC220V ±10%, 50 HZ |
Output voltage: |
60 KV |
Capacity: |
2.0 KVA |
Pressure increase speed: |
about 2 KV/S |
Voltage inspection accuracy: |
3% |
Dielectric strength sensitivity: |
<2KV |
Wave from distortion: |
3% |
Breakdown response time: |
10ms |
Polar distance: |
2. 5mm |
Working environment: |
temperature: 0 to 40 º C, humidity: 85% (Relative Humidity) |
Storage environment: |
temperature: -20 to 60 º C, humidity: 75% (Relative Humidity) |
Working Altitude: |
< 1500 meters. (If over 1500m, it can be customized) |
Test cell: |
Glass, volume 300 to 500 ml, with protective cover and stirrer. |
Electrodes: |
Stainless steel spherical 36 mm diameter/hemispherical 25 mm radius, 2.5 mm gap as per IEC-156.
|
Dimensions: |
Before packed: 475× 485 ×485 mm After packed: 490 × 495 × 495 mm |
weight: |
Net Weight: 45 KGS Gross Weight: 50 KGS |
Transformer Oil BDV Test & Technician questions
1) Clear sampling bottles or plastic bottles are not used for Transformer insulation oil sampling, Why?
An amber glass bottle is the preferred container. Clear glass bottles may be used but they shall be protected from direct light until ready to be tested. Plastic containers which are not reacted by the transformer oil (to be tested) may be used, but these shall not be used more than once. For sealing, screw caps with polyolefin or polytetrafluoroethylene are preferred.
2) What is the standard method for sampling insulation oil?
When sampling, Containers should be almost filled with samples, leaving about 3% of the container volume as free air space.
Precautions shall be taken to avoid contamination of the sample. Do not talk while taking samples. It is not recommended to collect samples during windy, rainy, dusty, high humid, or very cold conditions.
Refer: IEC 60475
3) Is it ok, to collect the hot oil sample immediately after oil processing?
Yes. It is possible to collect for testing. But it is recommendable to collect the oil sample after it is cool down to ambient temperature.
However, at the time of test, the temperature of the insulation oil and ambient temperature shall not differ by more than 5°C
4) Where to collect the oil sample for BDV test, transformer top or bottom?
Transformer tank bottom.
Unless otherwise required, the sample is taken where the liquid is likely to be most contaminated, usually at the lowest point of the transformer tank.
The same location should be used each time a sample is collected to ensure it represents the historic trend.
5) What details shall be provided along with the Transformer Oil sample collection container?
Date of sampling, Project /Station Name, Area/ Unit No., Equipment Description, Equipment Make, Year of Make, Equipment Tag No/Serial No., Equipment rating (voltage), Oil Type, Oil Temperature, Reason for the test, Collection point, collected by (name).
6) What is the method of cleaning the sampling bottles after the test?
Containers shall be rinsed with acetone, traces of which shall be removed by blowing with warm air. After cleaning, containers shall be immediately capped and kept sealed until used.
7) What is the IEC standard for the Insulation oil Breakdown Voltage (BDV) Test?
IEC 60156
8) What are the acceptable criteria for the BDV test result?
Acceptance criteria are different for new (unused) and used oils.
But for the acceptable limits, it is recommendable to follow project/utility specifications, if specified, or refer manufacturer’s O&M manuals.
one can refer to IEC 60296 (for unused) and IEC 60422 (in-service).
100KV Automatic Portable Transformer Oil Breakdown Voltage Tester Sets
100KV Automatic Portable Transformer Oil Breakdown Voltage Tester Sets
Since the foundation of our company, we have been devoting our efforts to developing better purifiers for energy saving. With the intellectual support form our first-rate oil purification experts and encouraged by the company's modern management mechanism, we have developed six series of products, including hundreds of oil purifier models with independent intellectual property and advanced purification technology. Our equipment can be applied to many fields, such as electric power, petroleum chemical, metallurgical industry, mining, aviation, shipping railway and so on.