Emergency LED Driver For Product With Internal Driver 8W BLD-AM08N-950400 (only used for non- isolated)
Features:
1. Listed for field installation-UL924 and CSA C22.2 NO.141
2. Selectable emergency power 3W,5W,8W
3. Universal input (100-277Vac)
4. Battery protections over voltage protection low voltage protection over temperature protection : ,
5. RoHS compliant
Specifications:
UL Listed For field or factory installation
Universal Input Voltage (100-277Vac,50/60Hz)
AC Input Current: 90mA max.
AC Input Power Rating: 6W max.
Output Current and Voltage: 400mA 95Vdc max.
Output Power: 8W max.
Illumination Time: ≥90 Minutes
Test Switch Charging Indicator Light Low Voltage,illuminated Test Switch.
Battery: High-Temperature,Miantenance-Free Ni-MH battery 5 Years Life Expectancy
Battery Charging Current: 250mA
Recharge Time: ≥24Hours
Temperature Rating Ambient: 0°C to 50°C (32°F to 122°F)
Dimensions: 9.25''x1.97''x1.8'' 235mmx50mmx46mm, 17.7'’ 450mm Flexible Conduit
Emergency LED Driver IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
1.Risk of fire or electric shock.Luminaire wiring and electrical parts may be damaged when drilling for installation of LED Emergency Backup.Check for enclosed wiring and components.
2.Risk of fire or electric shock.This LED Emergency Backup installation requires knowledge of luminaires electrical systems.If not qualifed,do not attempt installation.Contact a qualifed electrician.
3. Before installing make certain the , AC power to the fixture is off.
4.The electrical rating of this product is 100 277Vac.Installer must confirm that there is 100 277Vac the fixture before installation
5. To prevent electrical shock only mate unit connector after installation is complete and before the AC power to the fixture is back on
6. Do not use outdoors.
7. This LED Emergency Backup unit requires an un switched AC power source of 100 277Vac 50 60Hz The AC driver must be on the same branch circuit as the LED Emergency Backup unit
8. Do not let power supply cords touch hot surfaces.
9. Do not mount near gas or electric heaters.
10.Do not join battery pack connecter until all other wiring is complete and AC power is on.
11.Equipment should be mounted in locations and at heights where it will not be subjected to tampering by
unauthorized personnel.
12. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
13. Do not use this equipment for other than its intended use.
14. Use with grounded, UL Listed, dry or damp location rated fixtures.
SAVE THESE INSTRUCTIONS
Applications:
The emergency driver for product with internal driver.The BLD-AM08N-950400 BLD-AM08N-950400 can supply an LED lighting load of 8w for 90 minutes.
These emergency driver have been evaluated to and found compliant to UL 924 The emergency pack assembly is accepted as a component of a luminaire
where the suitability of the combination shall be determined by UL or Authorities Having Jurisdiction.The as installed performance of the system must meet or exceed all Federal State,and Local code requirements
Operation
AC Operation AC power is present. The AC driver operates the LED load as designed AC internal driver that has an input current not to exceed 2.0 A.The emergency pack is charging in a standby mode.The charging indicator will be lit showing that the battery is charging.
Emergency Operation When the AC power goes out the emergency pack detects the power outage and automatically switches to the emergency mode.The charging indicator will be off.The LED load is illuminated,for a minimum of 90 minutes When AC power is restored,The emergency pack switches back
to Normal Mode and starts re charging.
Manlfunction Mode:When the emergency driver internal circuit without fault and battery normal,The green
LED will be lit,When battery disconnected and the emergency driver circuit fault, the green LED off.