Triplex abc cable sizes PVC insulated wire and cables
Introduction of overhead insulated cable
Our overhead insulated cable have formed a system, such as single core, two-core, three-core and four-core. There are conductors of aluminum, copper or aluminum conductors steel-reinforced.
Application
To be used at voltage of 600V pahse-to -pahse or less and at conductor temperatures not to exceed 750C for polyethylene insulated conductor or 900C for crossliked polyethlene (XLPE) insulated conductors.
Cable's characteristics
1) Rated voltage U:10kV
2) Installing temperature should not be below -200C.
3) admissible bending radius to cable:
4) Admissible bending radius to cable should be not less than 20(d+D)±5%mm.
Where:D-real overall diameter of cable (mm). d-real diameter of conductor (mm)
Code word |
AWG or kcmil | Bare Neutral Messenger | Phase Conductor | Weight kg/km | ||||
ALLOY | Rated Strength Ibs | AAC | Insul Thick mm | |||||
Number | Dia mm | Number | Dia mm | |||||
Minex | 2*6AWG+1*30.58 | 7 | 1.68 | 1110 | 1 | 4.11 | 1.14 | 152 |
Sandcrab | 2*1/0AWG+1*77.47 | 7 | 2.67 | 2800 | 7 | 3.12 | 1.52 | 504 |
Echinus | 2*1/0AWG+1*77.47 | 7 | 2.67 | 2800 | 19 | 1.89 | 1.52 | 505 |
Crayfish | 2*2/0AWG+1*97.65 | 7 | 3.00 | 3530 | 7 | 3.50 | 1.52 | 621 |
Sipho | 2*2/0AWG+1*97.65 | 7 | 3.00 | 3530 | 19 | 2.13 | 1.52 | 622 |
Fulgar | 2*3/0AWG+1*123.3G | 7 | 3.37 | 4460 | 19 | 2.39 | 1.52 | 767 |
Arca | 2*4/0AWG+1*155.4 | 7 | 3.78 | 5390 | 19 | 2.68 | 1.52 | 949 |
Triplex service drop