Single phase oil immersed current transformer 132kv
Main criteria to follow
IEC standard IEC60044-1 "current transformer"
National standard: GB1208 "current transformer"
GB311.1" insulation coordination of high voltage transmission and transformation equipment"
Using environmental conditions
ambient temperature -40~+40℃
Altitude LB7-132(110,66) ( W1,W2,W3 )type no more than 1000m
LB7-132(110,66) GY( W2 ) type no more than 3000m
Environmental pollution level:II,III,IV Polluted area
Structure characteristics
Product use
This product provides 132 (110, 66) kv, An outdoor single-phase oil-immersed vertical current transformer is used in 50 or 60 Hz power system for current, power measurement and relay protection.
System general situation
System rated voltage:132lv 110kv 66kv
System maximum voltage:145kv 126kv 72.5kv
System rated frequency :50Hz or 60Hz
System neutral grounding mode: effective groundin
Rated primary voltage | 132(110, 66)kv |
Maximum voltage of equipment | 142(126, 72.5)kv |
Rated frequency | 50 or 60Hz |
Rated current ratio | 2X30~2X1000/5 or1A |
Number of two windings | 1~6 |
Measurement of winding accuracy | 0.2, 0.2s, 0.5, 0.5s |
Accuracy of protection winding | 5P or 10P |
Rated two output | 20-50VA |
Accuracy limit coefficient ALF | 15, 20, 25, 30 |
Instrument safety factor FS | ≤5 or 10 |
The PD level is under 1.2Um/√3KV. | <5PC |
The dielectric loss factor is from 10kV to Um/√ 3KV. | <0.005 increment <0.001 |
Rated power frequency withstand voltage | 230(275)kv 200(230)kv 140kv(Square root value) rms |
Rated lightning impulse withstand voltage | 550(650)kv 450(550)kv 325lv (Peak value) peak |
Rated power frequency withstand voltage of primary winding | 3kv(Square root value)rms |
Rated power frequency withstand voltage of ground screen to ground | 5kv(Square root value)rms |
Rated power frequency withstand voltage between two winding to ground and two winding | 3kv(Square root value)rms |
Interturn withstand voltage of two windings | 4.5kv(Peak value)peak |
Mechanical strength (three directions) | 2000N |
Rated primary current | Rated short-time thermal current | Rated dynamic stability current |
(A) | (KA) | (KA) |
30-60 | 3.15-6.3 | 7.9-15.8 |
50-100 | 5.3-10.6 | 13-26 |
75-150 | 7.9-15.8 | 20-40 |
100-200 | 10.5-21 | 27-54 |
150-300 | 15.8-31.5 | 40-80 |
200-400 | 21-42 | 54-108 |
300-600 | 31.5-45(3S) | 80-115 |
400-800 | 31.5-45(3S) | 80-115 |
500-1000 | 31.5-45(3S) | 80-115 |
600-1200 | 31.5-45(3S) | 80-115 |
750-1500 | 31.5-45(3S) | 80-115 |
800-1600 | 31.5-453S) | 80-115 |
1000-2000 | 31.5-45(3S) | 80-115 |
Product use
This product provides 220kv, An outdoor single-phase oil-immersed vertical current transformer is used in 50 or 60 Hz power system for current, power measurement and relay protection.
System general situation
System rated voltage: 220kv
System maximum voltage: 252kv
System rated frequency: 50Hz or 60Hz
System neutral grounding mode: effective grounding
Rated primary voltage | 220kv |
Maximum voltage of equipment | 252kv |
Rated frequency | 50 or 60Hz |
Rated current ratio | 2X300~2X1000/5 or1A |
Number of two windings | 1~8 |
Measurement of winding accuracy | 0.2,0.2s,0.5,0.5s |
Accuracy of protection winding | 5P or 10P |
Rated two output | 20-50VA |
Accuracy limit coefficient ALF | 15\20\25\30 |
Instrument safety factor FS | <=5 or 10 |
The PD level is under 1.2Um/√3KV. | <5PC |
The dielectric loss factor is from 10kV to Um/√ 3KV. | <0.005increment<0.001 |
Rated power frequency withstand voltage | 395kv(Square root value)rms |
Rated lightning impulse withstand voltage | 950kv(Peak value)peak |
Rated power frequency withstand voltage of primary winding | 3kv(Square root value)rms |
Rated power frequency withstand voltage of ground screen to ground | 5kv(Square root value)rms |
Rated power frequency withstand voltage between two winding to ground and two winding | 3kv(Square root value)rms |
Interturn withstand voltage of two windings | 4.5kv(Peak value)peak |
Mechanical strength (three directions) | 2500N |
Rated primary current | Rated short-time thermal current | Rated dynamic stability current |
(A) | (KA) | (KA) |
300-600 | 25-50 | 62.5-125 |
400-800 | 25-50 | 62.5-125 |
500-1000 | 25-50 | 62.5-125 |
600-1200 | 31.5-50(3S) | 80-125 |
750-1500 | 31.5-50(3S) | 80-125 |
800-1600 | 31.5-50(3S) | 80-125 |