Model | 6-CNF-200 |
Cells Per Unit | 6 |
Voltage Per Unit | 12 |
Capacity | 200Ah@20hr-rate to 1.75V per cell @25℃ |
Weight | Approx. 60.0 Kg (Tolerance±1.5%) |
Internal Resistance | Approx. 5.2 mΩ |
Terminal | F16(M8)/F10(M8) |
Max. Discharge Current | 2000A (5 sec) |
Design Life | 15 years (floating charge) |
Maximum Charging Current | 40.0A |
Reference Capacity | C3 136.5AH C5 151.5AH C10 174.0AH C20 200.0AH |
Float Charging Voltage | 13.6 V~13.8 V @ 25℃ Temperature Compensation: -3mV/℃/Cell |
Cycle Use Voltage | 14.2 V~14.4 V @ 25℃ Temperature Compensation: -4mV/℃/Cell |
Operating Temperature Range | Discharge: -40℃~60℃ Charge: -20℃~50℃ Storage: -40℃~60℃ |
Normal Operating Temperature Range | 25℃±5℃ |
Self Discharge | SUNPAL Valve Regulated Lead Acid (VRLA) batteries can be stored for up to 6 months at 25℃ and then recharging is recommended. Monthly Self-discharge ratio is less than 3% at 25℃.Please charged batteries before using. |
Container Material | A.B.S. UL94-HB, UL94-V0 Optional. |
F.V/Time | 15MIN | 30MIN | 1HR | 2HR | 4HR | 8HR | 10HR | 20HR |
1.60V | 273.6 | 183.4 | 111.8 | 66.9 | 37.9 | 21.4 | 18.1 | 11.0 |
16.5V | 268.0 | 181.8 | 111.3 | 66.4 | 37.7 | 21.2 | 17.9 | 10.6 |
1.70V | 263.8 | 180.7 | 110.2 | 65.9 | 37.5 | 21.0 | 17.7 | 10.3 |
1.75V | 254.1 | 177.9 | 109.2 | 65.4 | 37.2 | 20.8 | 17.5 | 10.0 |
1.80V | 237.0 | 171.7 | 106.6 | 64.2 | 36.3 | 20.5 | 17.4 | 9.40 |
1.85V | 215.0 | 162.4 | 101.3 | 61.4 | 34.6 | 19.6 | 16.8 | 9.00 |
F.V/Time | 15MIN | 30MIN | 1HR | 2HR | 4HR | 8HR | 10HR | 20HR |
1.60V | 502 | 348 | 215 | 131 | 75.3 | 42.5 | 36.0 | 19.5 |
16.5V | 494 | 344 | 215 | 131 | 75.2 | 42.3 | 35.8 | 19.1 |
1.70V | 488 | 345 | 213 | 130 | 75.0 | 42.0 | 35.4 | 18.8 |
1.75V | 471 | 341 | 211 | 129 | 74.3 | 41.7 | 35.1 | 18.4 |
1.80V | 440 | 330 | 207 | 127 | 72.6 | 41.0 | 34.7 | 18.1 |
1.85V | 401 | 313 | 198 | 123 | 69.1 | 39.3 | 33.7 | 17.0 |