- intermediate relay used for switching larger load output, strengthen or multiplying contacts of the existing device.
Technical parameters | R8-116 | R8-208 | R8-308 | R8-316 |
Supply terminals | A1-A2 | A1-A2 | ||
Voltage range |
AC/DC 12V,24V,48V,110V
|
AC/DC 12V,24V | ||
Burden |
AC.max 3VA/DC.max1.2W
|
|||
Supply terminals |
A1-A2-A3
|
A1-A2 | ||
Voltage range |
AC230V(A1-A2) AC/DC24V(A1-A3)
|
AC230V
|
||
Burden |
AC.max 3VA/DC.max1.2W
|
AC.max 3VA
|
||
Supply voltage tolerance | -15%;+10% | |||
Max.chargeover time
|
10ms
|
|||
Output
|
||||
Number of contact
|
1×SPDT | 2×SPDT | 3×SPDT | 3×SPDT |
Current rating | 16A/AC1 | 8A/AC1 | 16A/AC1 | |
Switching voltage | 250VAC/24VDC | |||
Min.breaking capacity DC | 500mW | |||
Output indication | Red LED | |||
Mechanical life |
1×107 |
|||
Electrical life(AC1) | 1×106 | |||
Reset time | max.200ms | |||
Operating temperrature | -20℃ to +55℃(-4℉ to 131℉) | |||
Storage temperature | -35℃ to +75℃(-22℉ to 158℉) | |||
Mounting/DIN rail | Din rail EN/IEC 60715 | |||
Protecting degree | IP40 for front panel /IP20 terminals | |||
Operating position | any | |||
Overvoltage category | Ⅲ. | |||
Pollution degree | 2 | |||
Max.cable size(mm²) | soild wire max.1×2.5 or 2×1.5/with sleeve max.1×2.5(AWG 12) | |||
Dimensions | 90×18×64mm | |||
Weight | 44g/54g | 50g/60g | 72g/82g | 86g/86g |
Standards | IEC/EN 61810-1,IEC/EN61010-1 |
Wiring Diagram