PVC Fill Infill For Marley Cooling Tower
Introduction:
Cooling tower fill is one of the most important components for exchange of gas and water in cooling tower. It is the major parts to improve the efficiency of cooling tower and make sure the economic and safe operation.
Our cooling tower fill are widely used in different types of cooling towers and evaporative condensers. And have the following advantages:
1. Great performance of heat dissipation
2. Anti-aging, long service time
3. Little wind resistance coefficient
4. Difficult deformation
Technical Data:
|
Length(mm) |
Height(mm) |
Film thickness(mm) |
|||
Size |
Tolerance |
Size |
Tolerance |
Size |
Tolerance |
|
“S” Wave |
1000 |
±10 |
500 250 |
±5 |
0.4 |
±0.05 |
2000 |
±10 |
500 250 |
±5 |
0.4 |
±0.05 |
|
Double Inclined |
1000 |
±10 |
500 250 |
±5 |
0.4 |
±0.05 |
Inclined Wave |
1000 |
±10 |
500 |
±5 |
0.4 |
±0.05 |
|
Fill Height |
Cooling No. (Volume Scattered Coefficient: Ka) |
Resistance Equotion:P/p1=9.81*A*Vcpm A.M expression |
“S” Wave |
1m |
=1.83y0.65 |
A=-0.0019q2+0.0685q+0.06543 |
Ka=4746g0.56q0.36 |
M=-0.0028q2-0.0170q+1.9480 |
||
Double Inclined |
1m |
=1.92y0.68 |
A=-0.0006q2+0.0306q+0.06376 |
Ka=4342g0.69q0.36 |
M=-0.0002q2-0.0026q+1.9029 |
||
Inclined Wave |
1m |
=1.85y0.64 |
A=-0.0001q2+0.189q+0.6374 |
Ka=4296g0.63q0.38 |
M=-0.0006q2-0.0122q+2.0178 |
Heng An has come a long way since it was established in 1975, and now has 900+ employees. Company total assets has reached to USD160 million. Heng An Cooling is one of the largest manufacturers of cooling towers, evaporative condensers and air coolers in China. For more than 40 years, we have provided exceptional quality euqipment and service to the industrial, refrigeration and power generation markets.