Features:
ORDER NO. | GSM220A12-R7B | GSM220A15-R7B | GSM220A20-R7B | GSM220A24-R7B | |
OUTPUT | SAFETY MODEL NO | GSM220A12 | GSM220A15 | GSM220A20 | GSM220A24 |
DC VOLTAGE | 12V | 15V | 20V | 24V | |
RATED CURRENT | 15A | 13.4A | 11A | 9.2A | |
CURRENT RANGE | 0 ~ 15A | 0 ~ 13.4A | 0 ~ 11A | 0 ~ 9.2A | |
RATED POWER (max.) | 180W | 201W | 220W | 221W | |
RIPPLE & NOISE (max.) | 80mVp-p | 100mVp-p | 150mVp-p | 180mVp-p | |
VOLTAGE TOLERANCE | ±5.0% | ±5.0% | ±4.0% | ±3.0% | |
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
LOAD REGULATION | ±5.0% | ±5.0% | ±4.0% | ±3.0% | |
SETUP, RISE | 2000ms, 50ms / 230VAC 2000ms, 50ms / 115VAC at full load | ||||
HOLD UP TIME (Typ.) | 20ms / 230VAC 20ms / 115VAC at full load | ||||
INPUT | VOLTAGE RANGE | 80 ~ 264VAC | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
POWER FACTOR (Typ.) | PF>0.91 / 230VAC PF>0.98 / 115VAC at full load | ||||
EFFICIENCY (Typ.) | 90% | 90% | 92% | 93.5% | |
AC CURRENT (Typ.) | 4A / 115VAC 2A / 230VAC | ||||
INRUSH CURRENT (Typ.) | 120A / 230VAC | ||||
LEAKAGE CURRENT(max.) | Earth leakage current < 100μ A/264VAC , Touch current <100μ A/264VAC | ||||
PROTECTION | OVERLOAD | 105 ~ 135% rated output power | |||
Protection type : Hiccup mode, recovers automatically after fault condition is removed | |||||
OVER VOLTAGE | 105 ~ 135% rated output voltage | ||||
Protection type : Shut down o/p voltage, re-power on to recover | |||||
OVER TEMPERATURE | Shut down o/p voltage, re-power on to recover | ||||
ENVIRONMENT | WORKING TEMP. | -30 ~ +70°C (Refer to "Derating Curve") | |||
WORKING HUMIDITY | 20% ~ 90% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40 ~ +85°C, 10 ~ 95% RH | ||||
TEMP. COEFFICIENT | ±0.03% /°C(0 ~50°C) | ||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes | ||||
SAFETY & EMC | SAFETY STANDARDS | ANSI/AAMI ES60601-1, TUV EN60601-1 approved | |||
ISOLATION LEVEL | Primary-Secondary: 2xMOPP | ||||
WITHSTAND VOLTAGE | I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | ||||
ISOLATION RESISTANCE | I/P-O/P:100M Ohms / 500VDC / 25°C/ 70% RH | ||||
EMC EMISSION | Compliance to EN55011(CISPR11) class B, EN61000-3-2,3, FCC PART 15 class B | ||||
EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN60601-1-2, EN61204-3 medical level, criteria A | ||||
OTHERS | MTBF | 208.66K hrs min. MIL-HDBK-217F(25°C) | |||
DIMENSION | 210*85*46mm (L*W*H) | ||||
PACKING | 1.1Kg; 12pcs/14.2Kg/0.73CUFT | ||||
CONNECTOR | PLUG | See page 3 ; Other type available by customer requested | |||
CABLE | See page 3 ; Other type available by customer requested |
ORDER NO. | GSM220A12-R7B | GSM220A15-R7B | GSM220A20-R7B | GSM220A48-R7B | |
OUTPUT | SAFETY MODEL NO | GSM220A12 | GSM220A15 | GSM220A20 | GSM220A4 |
DC VOLTAGE | 12V | 15V | 20V | 48V | |
RATED CURRENT | 15A | 13.4A | 11A | 4.6A | |
CURRENT RANGE | 0 ~ 15A | 0 ~ 13.4A | 0 ~ 11A | 0 ~ 4.6A | |
RATED POWER (max.) | 180W | 201W | 220W | 221W | |
RIPPLE & NOISE (max.) | 80mVp-p | 100mVp-p | 150mVp-p | 240mVp-p | |
VOLTAGE TOLERANCE | ±5.0% | ±5.0% | ±4.0% | ±2.0% | |
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
LOAD REGULATION | ±5.0% | ±5.0% | ±4.0% | ±2.0% | |
SETUP, RISE | 2000ms, 50ms / 230VAC 2000ms, 50ms / 115VAC at full load | ||||
HOLD UP TIME (Typ.) | 20ms / 230VAC 20ms / 115VAC at full load | ||||
INPUT | VOLTAGE RANGE | 80 ~ 264VAC | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
POWER FACTOR (Typ.) | PF>0.91 / 230VAC PF>0.98 / 115VAC at full load | ||||
EFFICIENCY (Typ.) | 90% | 90% | 92% | 94.5% | |
AC CURRENT (Typ.) | 4A / 115VAC 2A / 230VAC | ||||
INRUSH CURRENT (Typ.) | 120A / 230VAC | ||||
LEAKAGE CURRENT(max.) | Earth leakage current < 100μ A/264VAC , Touch current <100μ A/264VAC | ||||
PROTECTION | OVERLOAD | 105 ~ 135% rated output power | |||
Protection type : Hiccup mode, recovers automatically after fault condition is removed | |||||
OVER VOLTAGE | 105 ~ 135% rated output voltage | ||||
Protection type : Shut down o/p voltage, re-power on to recover | |||||
OVER TEMPERATURE | Shut down o/p voltage, re-power on to recover | ||||
ENVIRONMENT | WORKING TEMP. | -30 ~ +70°C (Refer to "Derating Curve") | |||
WORKING HUMIDITY | 20% ~ 90% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40 ~ +85°C, 10 ~ 95% RH | ||||
TEMP. COEFFICIENT | ±0.03% /°C(0 ~50°C) | ||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes | ||||
SAFETY & EMC | SAFETY STANDARDS | ANSI/AAMI ES60601-1, TUV EN60601-1 approved | |||
ISOLATION LEVEL | Primary-Secondary: 2xMOPP | ||||
WITHSTAND VOLTAGE | I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | ||||
ISOLATION RESISTANCE | I/P-O/P:100M Ohms / 500VDC / 25°C/ 70% RH | ||||
EMC EMISSION | Compliance to EN55011(CISPR11) class B, EN61000-3-2,3, FCC PART 15 class B | ||||
EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN60601-1-2, EN61204-3 medical level, criteria A | ||||
OTHERS | MTBF | 208.66K hrs min. MIL-HDBK-217F(25°C) | |||
DIMENSION | 210*85*46mm (L*W*H) | ||||
PACKING | 1.1Kg; 12pcs/14.2Kg/0.73CUFT | ||||
CONNECTOR | PLUG | See page 3 ; Other type available by customer requested | |||
CABLE | See page 3 ; Other type available by customer requested |
Mechanical Specification:
Packing:
Shipping:
Strict, professional production and test, large stock for fast shipping.
What Certification do we have?
What our Power Supply can do for you?
SUCCESS IS A RESULT OF OUR COMMITMENT TO A QUALITY SERVICE IN PARTNERSHIP WITH OUR CLIENTS
1. What we sell is 100% Genuine Mean Well Power Supply;
2. Small quantity orders acceptable;
3. We will choose the most suitable shipping way for you and inform you the cost advance, decision will be made by you;
4. We have larger stocks and this support us can make a very prompt shipping;
5. To assure you the maximum comfort and satisfaction, we accept pay via T/T, Paypal, Western Union;
6. Price could be negotiated for more and large quantity;
7. Your enquiry will be quickly responsed, we will choose the most suitable products and quote the most competitive price for you.
If you are interested in other models, please hit below links for details....