ELECTRICAL PERFORMANCE | ||
Nominal Voltage | 48V | |
Nominal Capacity | 100 Ah | |
Capacity @ 20A | 300 min | |
Energy | 5120 Wh | |
Communication | CAN2.0/RS232/RS485 | |
Resistance | ≤45 mΩ @ 50% SOC | |
Efficiency | >96% | |
Module Parallel | Up to 16 packs |
CHARGE PERFORMANCE | ||
Recommended Charge Current | 20A | |
Maximum Charge Current | 100A | |
Recommended Charge Voltage | 54V | |
BMS Charge Cut-Off Voltage | <54.7 V (3.65V/Cell) | |
Reconnect Voltage | >54 V (3.6V/Cell) | |
Balancing Voltage | <54V (3.6V/Cell) | |
Maximum Batteries in Series (cells) | 15(*Consult MUST) |
DISCHARGE PERFORMANCE | ||
Maximum Continuous Discharge Current | 100 A | |
Peak Discharge Current | 110 A (3s) | |
BMS Discharge Cut-Off Current | 150 A (300ms) | |
Balancing open voltage | 51.7V (3.45V/Cell) | |
Recommended Low Voltage Disconnect | 41.2 V (2.75V/Cell) | |
BMS Discharge Cut-Off Voltage | >30.0V (2s) (2.0V/Cell) | |
Reconnect Voltage | >37.5 V (2.5V/Cell) | |
Short Circuit Protection | 250 ~ 500 μs |