Max working temperature | 70℃ for PVC:insulation and 90℃ for XLPE insulation |
Max temperature | 160℃ for PVC:insulation , 250℃ for XLPE insulation |
Environment temperature | Cable lowest environment temperature - 10 ℃. |
Installation | When installing laying temperature, laying temperature should not below 0 ℃. |
Recommended minimum bending radius | Single core cable bending radius is less than 20 d, multi-core cable bending radius less than 150. |
Scope of application | This product is suitable for use in ac 50 hz, rated voltage 0.6/1 KV line (the highest voltage 1.2 KV) system in the power transmission in the power line. |
Delivery time | Within 7-10 days after receiving your payment |
Payment term | T/T or L/C |
Cross section | Single wire quantity in conductor | Insulation thickness | External diameter | Sheath thickness | Conductor resistance at 20 dc Cu | Testing voltage |
mm 2 | mm | mm | mm | Ω km | kv/5min | |
1.5 | 1 | 0.8 | 6.1 | 1.4 | 12.1 | 3.5 |
2.5 | 1 | 0.8 | 6.5 | 1.4 | 7.41 | 3.5 |
4 | 1 | 1.0 | 7.4 | 1.4 | 4.61 | 3.5 |
6 | 1 | 1.0 | 7.9 | 1.4 | 3.08 | 3.5 |
10 | 7 | 1.0 | 9.2 | 1.4 | 1.83 | 3.5 |
25 | 7 | 1.2 | 12 | 1.4 | 0.727 | 3.5 |
35 | 7 | 1.2 | 13.2 | 1.4 | 0.524 | 3.5 |
50 | 19 | 1.4 | 14.9 | 1.4 | 0.387 | 3.5 |
70 | 19 | 1.4 | 16.7 | 1.4 | 0.268 | 3.5 |
95 | 19 | 1.6 | 19.3 | 1.5 | 0.193 | 3.5 |
120 | 37 | 1.6 | 20.9 | 1.5 | 0.153 | 3.5 |
150 | 37 | 1.8 | 23.1 | 1.6 | 0.124 | 3.5 |
185 | 37 | 2.0 | 25.6 | 1.7 | 0.0991 | 3.5 |
240 | 61 | 2.2 | 28.8 | 1.8 | 0.0754 | 3.5 |
300 | 61 | 2.4 | 31.9 | 1.9 | 0.0601 | 3.5 |
400 | 61 | 2.6 | 35.5 | 2.0 | 0.0470 | 3.5 |
500 | 61 | 2.8 | 39.7 | 2.1 | 0.0366 | 3.5 |
630 | 91 | 2.8 | 43.7 | 2.2 | 0.0283 | 3.5 |