LB6-110 Current transformer is oil-immersed ,Outdoor type .
It can be used for the electric current measurement
energy measurement and replay protection in the electric
power system with a voltage of rated voltage 110kV
and for requency of 50/60Hz
The products are in accordance with the requirements of the standard :
GB1208”Current Transformer’ and IEC60044-1’Current Transformer ‘
It is divided into conventional type and cast aluminum type according to
the materialof oil tank . The customers can choose as their requirement
Ambient temperature :Max.temperature :+40℃;
Min.temperature :-25℃(- 45℃)
Daily are average temperature : no more than : 30℃
Altitude : no more than 2000m (unless otherwise specified)
Max.wind velocity : no more than 34m/s
Operation Conditions
Rated voltage | 110KV |
Rated frequency | 50/60Hz |
Rated insulation level | 126/230/550KV |
Creepage distance | 3155mm |
Flashover distance | 1150mm |
Rated short-time thermal curent (kA) | 5.3~45kA/3s |
Rated dynamic stability current (kA) | 13~115 |
Rated primary current (A) | 50~3200A |
Rated secondary current (A) | 1 or 5 |
Accuracy class | 0.2,0.2S,0.5,0.5S,5P,10P any combinations |
Rated burden (VA) | 15~60VA |
Instrument security factor(FS) | ≤5 or 10 5 or 10 |
Accuracy limit factor | 10,15,20,30 |
Mounting hole dimension (mm) | 4 X 18 |
Mounting dimension (mm) | 475 X 475 |
Oil weight /Total weight (kg) | 120/450 |
Outline Dimensions (mm) | (695±15) X570X (2150±15) |