•Technical data
Current rating range 5~30A
Input voltage rating 125/250VAC; 32/50VDC
Interrupting Capacity 125/250VAC x 1,000A(UL 1077)
Typical life 1,000 operations at 200% overload
Insulation co-ordination Rated impulse withstand voltage 2.5kV
Dielectric Strength > 1,500VAC/min.
Insulation Resistance >100MOHM (DC 500V)
Degree of protection operating area IP40
•Mechanical/Environmental Data
Operating Ambient Temperature: -10 to +60℃℃
Termination: 250’’(6.35mm)quick connects or solder terminals
Mounting: Various options. See Ordering Information and drawings
•Typical applications
Tarnsforms, Motors, Battery chargers, Power supplies,
appliances, extra low voltage systems, machinery.
•Calibration(at25℃)
•100% of Rated Current: Hold , No Trip
•300% of Rated Current: 1.5-5.0 sec Trip
•200% of Rated Current: 5-30 sec Trip
•150% of Rated Current: Trip Within 1 Hour
•Approval & File No. Rated current Rated voltage
•CUL UL E155159 3-50A 125/250VAC; 50VDC
•TUV SUD B15 09 58611 0073-30A 125/250VAC; 32VDC
•CCC 201101030752058 3-30A 125/250VAC.
•VDE 40036160 3-16A 125/250VAC
•CSA 102199 3-30A 125VAC