50Hz 6kw-30kw power with Japan Kubota Diesel Generator
Kubota diesel generator widely used in the area of industry, railway and construction. The engine is imported from Japan. The global service net of Superwatt and Kubota can provide our customers with reliable and guaranteed service.
Diesel generator set power with Japan Kubota engine and Stamford/ Leorysomer / Marathon / Meccalte alternator
Our company provides a full line of brand new and high quality products which are strictly tested before shipment.
Quality warranty is according to our standard conditions: 1year or 1500hours
Kubota Powered Single phase 3 cylinder 6.5kw 62DB Water cooled Diesel Engine generator Set
Generator set
GENSET TYPE | RATED | STANDBY | ENGINE | ALTERNATOR |
KW/KVA | KW/KVA | MODEL | MODEL | |
GF2-K8 | 6/7.5 | 6.6/8.3 | D905 | PI 044D |
GF2-K11 | 8/10.0 | 8.8/11.0 | D1105 | PI 044E |
GF2-K15 | 10.8/13.5 | 12/15.0 | V1505 | PI 044F |
GF2-K17 | 12/15.0 | 13/16.5 | D1703 | PI 044F |
GF2-K23 | 17/21.2 | 19/23 | V2203 | PI 044H |
GF2-K28 | 20.6/25.7 | 23/28 | V2003-T | PI 144D |
GF2-K38 | 27.5/34.4 | 30/38 | V3300 | PI 144G |
GF2-K47 | 34/42.5 | 37/47 | V3300-T | PI 144H |
prime Power:
This rating is for the supply of continuous electrical power (at variable load). There is no limit on the annul hours of operation and 10% overload power can be supplied for 1 hour in 12.
Standby Power:
This rating is for the supply of continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted.
Rated Voltage:
Available with customer requirements.
Kubota Engine
Alternator
Other alternator option: Leroy Somer
Control System
Harsen GU601A Genset Controller
Description:
The GU601A is an Automatic Start Control Module designed to automatically start and stop the Generator.The module also monitors and protects the engine, indicating operational status, fault conditions and metering on the front panel LCD and LED’s.
1.Configuration of parameters by front panel push buttons or by PC via mini USB interface with license free software.
2.Configurable fuel output energise to stop energise to run.
3.3Configurable inputs.
4.3 Configurable outputs.
5.2 Analogue inputs configurable for different senders for oil pressure and engine temperature.
6.True RMS measuring