Size (mm) | ||||||||
Width | 14.5 | Hight | 100 | |||||
Length | 102.6 | Case Color | Black | |||||
Case Material | PC+PPT | Protection | IP20 | |||||
Environment condition | ||||||||
Working Temperature | -20~+60℃ | Ambient Temperature | -40~+80℃ | |||||
Storage Temperature | 5 ~ 95% RH (non condensing) | |||||||
Input (Intrinsically safe) | ||||||||
Current input | 4~20mA ; 0~20mA | Input Resistance | ≥25Ω | |||||
Distribution voltage to transmitter | ≥16V (at 20mA) |
Output | ||||||||
Current Output | 4~20mA ; 0~20mA | Output Ripple | <10mV p-p | |||||
Current output load | Adaptive load 0 ~ 300 Ω ( Factory default) | |||||||
Power supply | ||||||||
Rated voltage | 24VDC | Supply voltage range | 20~30VDC | |||||
Maximum current consumption | ·<40mA (1-Input,1-Output) ·<50mA (1-Input,2-Output) ·<60mA (1-Input,3-Output) ·<70mA (1-Input,4-Output) ·<80mA (2-Input,2-Output) ·<90mA (2-Input,3-Output) ·<100mA(2-Input,4-Output) | |||||||
General Parameters | |||||||
Standard accuracy | ±0.1%FS | Thermal Drift | ±0.015% / ℃ | ||||
Power on or storage time drift | ±2μA (180days) | Response Time | <10ms | ||||
Impact of load change | ±2μA | ||||||
Electrical isolation | 2500V AC RMS / 1min | ||||||
Electromagnetic compatibility (EMC) | According to IEC 61326-1 (GB / T 18268), IEC 61326-3-1 | ||||||
LED indication | Green LED on when power supply is normal | ||||||
Power protection | Power supply reverse connection protection, power on impact protection, startup delay > 20ms | ||||||
Installed in a safe zone, it can be in Zone 0, zone 1 and zone 2; IIC、IIB、IIA; T4 ~ T6, connected with intrinsically safe equipment in dangerous area | |||||||
Field equipment suitable for connection | Transducer (Transmitter) or current source signal | ||||||
Installation method | It can be installed horizontally or vertically on the standard 35mm DIN rail. (products with rail power supply mode are installed on the special bus backplane type power supply DIN rail.) | ||||||
Explosion proof electrical standard | [Ex ia Ga] IIC 符合GB 3836.1、GB 3836.4、GB 3836.20 |
Function | Model codes | Descriptions | ||||||
Basic Model | XSA-PI | Intrinsic Safety Barrier for distribution or current input. | ||||||
XSA-PD | Dual channel, distribution input safety barrier (only suitable for the option of 2-in-2-out channel) | |||||||
XSA-II | Dual channel, current input safety barrier (only suitable for the option of 2-in-2-out channel | |||||||
Special Function | H | HART (only available for | ||||||
Default, no special function required. | ||||||||
Channel Mode | 11 | 1-input,1-output | ||||||
12 | 1-input,2-output | |||||||
22 | 2-input,2-output | |||||||
Input signal | A | 0 ~ 20mA or 4 ~ 20mA | ||||||
Output signal | A | 0 ~ 20mA or 4 ~ 20mA | ||||||
Z | tailored signal (see Note 1) | |||||||
Power supply | V1 | Power supply (Wiring by terminal blocks) 20~30VDC | ||||||
V2 | Power rail 20~30VDC (see Note 2) | |||||||
Note: |
Model selection example: Example 1: XSA-PIH11-AA-V1 ... 1-input and 1-output, power distribution or current input safety barrier, HART pass, current signal 0 / 4 ~ 20mA, terminal power supply 20 ~ 32vdc. Example 2: XSA-PIF12-AA-V1 ... 1-input 2-output, power distribution or current input safety barrier, with line fault alarm, current signal 0 / 4 ~ 20mA, terminal power supply 20 ~ 30VDC. Example 3:XSA-PD22-AA-V1... 2-input and 2-output, power distribution input safety barrier, current signal 0 / 4 ~ 20mA, terminal power supply 20 ~ 30VDC. Example 4: XSA-II22-AA-V2... 2 in 2 out, current input safety barrier, current signal 0 / 4 ~ 20mA, rail power supply 20 ~ 30VDC. Optional Accessories: Special power supply DIN rail: PSDR-3000 series | ||||||||