Product standard
China National GB/T12706-2008
Application
1.There are no drop-height restriction when laying cable,the environment temperature should not be less than 0℃.
2.The minimum bending radius of cable is as follows;
Item |
Single core |
Multiple core |
||
|
Non-armoured |
Armoured |
Non-armoured |
Armoured |
Min.bending radius |
20D |
15D |
15D |
12D |
Near joint box or cable terminal |
15D |
12D |
12D |
10D |
3.Working temperature of the cable:
For PVC sheathed,it is not more than 90℃.For PE sheathed,it is not more than 80℃
4.The highest working temperature of conductor is 90℃.When short circuit (the lasting time is not over 5s) ,the temperature is not more than 250℃.
The lasting time for the cable grounding fault is as follow:Type 1:1 min.and below for each grounding fault.
Type 2: Except Type1,the lasting time of the grounding fault for the single- -ogase is not more than 2 hours, the max.is not more than 8 hours. The annual lasting time of the grounding fault is not more than 125 hours.
Cable type,name and application
Type |
Description |
Application |
|
Cu |
Al |
||
YJV22 |
YJLV22 |
Steel tape armored,XLPE insulated and PVC sheathed power cable |
Laid underground,cable can bear mechanic force,but should not bear large breaking force. |
YJV32 |
YJLV32 |
Steel wire armored,XLPE insulated and PVC sheathed power cable |
Laid in water or soil with drop height,the cable can bear mechanic force and large breaking force. |
Structure size,reference weight and main technical parameters
0.6/1KV 4-core,cross-linked PE insulated,PVC sheathed power cable
Grade and choose for the using location:
1. Low-smoke free/Low-halogen types divides into four kinds: special class, first class, second class, third class according to theusingpropertv,fire damage and evacuationkextinguishment difficulty. Meanwhile it aslo complies.
2. When thev are laving in colligation, the low-smoke free/low-halogen wires and cables should be flame-retardancr rypes whose grades comply. If the location needs intergrated lines and constant electr icity under the outside fire, they should be fire resistance types.