* Online double-conversion
* DSP technology guarantees high reliability
* True galvanic isolation transformer design
* Control designed to withstand all kinds of loads
* Intelligent battery management to prolong battery lifecycle
* Independent ventilation enhance durable operation under harsh environment
* Adjustable battery numbers
* Accept dual-mains input
* Parallel operation with up to 4 units (option)
* Varieties of communication options available
* Optional 7" touch LCD
* Reverse phase frequency operation and supports non-neutral input
MODEL |
G33- 10KL |
G33- 15KL |
G33- 20KL |
G33- 30KL |
G33- 40KL |
G33- 60KL |
G33- 80KL |
G33- 100KL |
G33- 120KL |
G33- 160K |
G33- 200KL |
|
CAPACITY | 10 KVA / 8 KW |
15KVA / 12KW |
20 KVA / 16 KW |
30 KVA / 24 KW |
40 KVA / 32 KW |
60 KVA / 48 KW |
80 KVA / 64 KW |
100 KVA / 80 KW |
120 KVA / 96KW |
160 KVA / 128KW |
200 KVA / 160KW |
|
INPUT | ||||||||||||
Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||||||||
Acceptable Voltage Range |
285VAC ~ 475VAC | |||||||||||
Frequency | 50/60 Hz ± 10 % | |||||||||||
INVERTER | ||||||||||||
Nominal Voltage | 3 x 380VAC/400VAC (3Ph + N) | |||||||||||
Precision | Stationary: ±1% Transitory: ±5% (load variations 100-0-100%) |
|||||||||||
Frequency | 50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz | |||||||||||
Maximum Synchronization Speed |
±1 Hz/s | |||||||||||
Waveform | Pure Sine Wave | |||||||||||
Total Harmonic Distortion (THDv) |
<2% (Linear Load) ; <5% (Non-linear Load) | |||||||||||
Phase Displacement | 120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load) | |||||||||||
Dynamic Recovery Time |
3 cycles at 90 % of the static value | |||||||||||
Admissible Overload |
110% ~ 150% 10 min ~ 60 sec ; 150% ~ 160% 60 sec~ 200ms ; >160% 200ms | |||||||||||
Admissible Crest Factor |
3:1 | |||||||||||
Admissible Power Factor |
0.6~1 (inductive or capacitive) | |||||||||||
Imbalance Output Voltage @ 100% Unbalanced Load |
<1% | |||||||||||
Current Limit | High overload, short-circuit: RMS Voltage Limit High Crest-Factor current: Peak Voltage Limit | |||||||||||
STATIC BYPASS | ||||||||||||
Type | Solid state | |||||||||||
Voltage | 176VAC ~ 264VAC (Ph-N) ; 304VAC ~ 456VAC (Ph-Ph) | |||||||||||
Frequency | 50/60 Hz ± 10 % | |||||||||||
Activation Criterion | Microprocessor control | |||||||||||
Transfer Time | Zero | |||||||||||
Admissible Overload | 0% ~ 150% continuous working ; 150% ~ 180% 60 min~5 min ; >180% 5 min | |||||||||||
Transfer to Bypass | Immediate, for overloads above 160% | |||||||||||
Retransfer | Automatic after alarm clear | |||||||||||
MAINTENANCE BYPASS | ||||||||||||
Type | Without interruption | |||||||||||
Voltage | 3 x 400V (3Ph + N) | |||||||||||
Frequency | 50/60 Hz | |||||||||||
Overall Efficiency |
Line Mode |
89% | 90% | 91% | 92% | |||||||
Battery Mode |
90% | 91% | 92% | 93% | ||||||||
BATTERY & CHARGER | ||||||||||||
Battery Type and Numbers |
12VDC x 32 pcs (29~32 pcs adjustable) | |||||||||||
Nominal Battery Voltage |
384 VDC (Based on 32 pcs batteries) | |||||||||||
Charging Method | CC/CV | |||||||||||
Precision | ±1% | |||||||||||
Charging Current |
Default 10A, *Maximum = Capacity (KW) / Battery (real-time). |
Default 10A; Maximum 40A; 5A@ full load | ||||||||||
Charging Voltage | 432 VDC (Based on 32pcs batteries) | |||||||||||
PHYSICAL | ||||||||||||
Dimensions, D x W x H (mm) |
656 x 405 x 817 | 656 x 405x 941 | 821 x 432 x 1159 | 975 x 554 x 1286 | 975 x 554 x1326 | 1051 x 705 x 1646 | ||||||
Net Weight (Kgs) | 118 | 120 | 145 | 193 | 278 | 365 | 471 | 573 | 650 | 760 | 790 | |
STANDARD | ||||||||||||
EMC/Safety | CE, IEC 61000-4-5 Protection surge, IEC 62040-2 EMC/EMI, IEC62040-1 Safety |