* TrueOnline Double Conversionwith DSPControl
Double conversion between input / output, battery and bypass are totally isolated power line noise, spikes
and transients. A Digital Signal Processor (DSP) control provides an improved solution with high performance.
* Robust Electrical Performance to Prevent DamagefromTopand Bottom Connections
This UPS is designed to accept wide input voltage and frequency range to cope with the worst utility conditions.
It can eliminates harmful distortion from utility power and withstand all kinds of severe impacts from various loads.
It’s capable to support heavy duty equipment, production equipment and DCS (Distributed Control System) system.
* Screwless Cabinet Design and fully Coating PCBAsto Withstand Harsh Environment
The outside cabinet is designed only with locks without any screws and all PCBAs are coated for anti-moisture,
anti-electric leakage, anti-dust and anti-corrosion. Its robust design is suitable for harsh environment with
high temperature, high humidity, dense dust, salt, or fierce vibration.
* Unique Ventilation Design for Effective Heat Dissipation
Unique ventilation design allows heat to rise by the process of convection.
Therefore, the UPS cabinets can be added in parallel side by side for space-saving.
* Flexible Battery Configuration Adapts Different Applications
The number of batteries can be adjusted flexibly according to different power demands.
* Accepts Dual-mains Inputs
Giant Industry series is allowed to connect two separate power inputs to increase operation reliability.
* Frontaccess makes Maintenance and Replacement Easy
It's considerate to allow easy access to all of the electronic cards and power components in the unit through
the front panel for further maintenance and replacement.
* High Short-circuit and Overload
This UPS is built-in high short-circuit protection.Once short circuit occurs, this mechanism will be activated.
The load will stay protected and the UPS will remain intact. High overload protection supports 110% for 60 minutes
and 125% for 10 minutes.
* Easy integration into Existing Electrical Networks orGenerator
During wiring connection, Giant industry can be accessible either from top or from bottom under different
environmental conditions. Besides, this UPS is fully compatible with generator.
* Parallel Capability up to 4 units
Up to 4 units in parallel can be operated without adding additional hardware, increasing system capacity as well as
operation reliability for power redundancy.
Giant Industry 3Ph-in / 1Ph-out 220VDC Industrial Online UPS Selection Guide
MODEL | I31-10KL | I31-15KL | I31-20KL | I31-30KL | I31-40KL | I31-60KL | I31-80KL | I31-100KL | I31-120K | |
CAPACITY |
10KVA/ 8KW |
15KVA/ 12KW |
20KVA/ 16KW |
30KVA/ 24KW |
40KVA/ 32KW |
60KVA/ 48KW |
80KVA/ 64KW |
100KVA/ 80KW |
120KVA/ 96KW |
|
INPUT | ||||||||||
Nominal Voltage | 3 x 380VAC (3Ph + G or 3Ph + N + G) | |||||||||
Acceptable Voltage Range |
304VAC ~ 456VAC | |||||||||
Frequency | 50Hz ±5 Hz (±10%) | |||||||||
OUTPUT | ||||||||||
Nominal Voltage | 220VAC/230VAC/240VAC (Selectable) | |||||||||
Connection Type | Hardwire 3-wire (1Ph+N+G) | |||||||||
Waveform | Pure Sine Wave | |||||||||
Output Voltage |
Steady state |
±1% | ||||||||
Transient state |
±5% | |||||||||
Frequency | 50 Hz | |||||||||
Frequency Stability |
± 1% | |||||||||
Frequency Synchronisation Range |
± 5Hz (Equal to bypass working range) | |||||||||
Frequency Synchronisation Speed |
1~2 Hz/s | |||||||||
Power Factor | 0.8 | |||||||||
Crest Factor | 3:1 | |||||||||
Total Harmonic Distortion (THDv) |
<2% (Linear Load) <4% (Non-linear Load) |
|||||||||
Dynamic in-rush Voltage Range |
0%->100%->0% (R Load) <±5% : 20%->100%->20% (R Load) ±3% | |||||||||
Dynamic Recovery Time (III Grade) |
0%~100% RCD load : <60 ms recover to 90% of nominal voltage | |||||||||
Phase Displacement |
120º ±1% (balanced load) 120º ±2% (imbalances 50% of the load) |
|||||||||
Transfer Time | 0 ms | |||||||||
Overload Capability |
0% ~ 110% continuous running; 110% ~ 150% for 10 min~1 min; >160% for 200ms | |||||||||
Short-circuit Capability |
60~100ms | |||||||||
Transient Response Time |
< 5ms | |||||||||
BYPASS | ||||||||||
Connection Type |
Hardwire 3-wire (1Ph+N+G) | |||||||||
Input Voltage Range |
220VAC ± 25% | |||||||||
Overload / Short-circuit capability |
1.5 In~1.8 In 1h~30s | |||||||||
1.8 In ~ >2.0 In 30s~200ms | ||||||||||
SYSTEM | ||||||||||
Efficiency (@ linear load) |
≥90% | |||||||||
ECO Mode (Non-parallel models) |
Yes | |||||||||
EPO Function | Yes | |||||||||
BATTERY & RECTIFIER | ||||||||||
Rectifier | Type | 6 pulse | 12 pulse | |||||||
Rated Output Voltage |
220 VDC | |||||||||
Charger Voltage |
216VDC ~ 243VDC (Adjustable) | |||||||||
Charging Current (maximum) |
Default 10A, Maximum = Capacity / Battery Voltage |
Default 10A, Maximum 40A | ||||||||
Battery | Type | Support VRLA Battery | ||||||||
Numbers | 16 - 18 pcs (adjustable) | |||||||||
Reverse Diode |
Yes | |||||||||
Cold Start |
Yes | |||||||||
PHYSICAL | ||||||||||
IP Protection | IP20 (Default), IP21/IP31 (Option) | |||||||||
Dimensions, DxWxH (mm) |
800 x 800 x 1800 | 800 x 1200 x 1800 | 800 x 1600 x 1800 | |||||||
Net Weight (Kgs) |
354 | 386 | 400 | 480 | 680 | 910 | 1010 | 1360 | 1620 | |
ENVIRONMENT | ||||||||||
Operating Temperature |
0~ 35°C continuous running, 40°C 8-hour running at nominal input voltage, recharging batteries and no overload, 45°C derating to 85% with linear load |
|||||||||
Operating Humidity |
0~90% (non-condensing) | |||||||||
Noise Level | Less than 70dB @ 1 Meter | |||||||||
MANAGEMENT | ||||||||||
Modbus RS-232/ RS485 |
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC | |||||||||
Dry Contacts | 6 outputs and 2 inputs | |||||||||
Optional SNMP | Power management from SNMP manager and web browser | |||||||||
STANDARD | ||||||||||
EMC/Safety | IEC 61000-4-5 Surge Protection, IEC 62040-2 EMC/EMI, IEC62040-1 Safety |