GLG 4-20mA Analog Signal Isolator Isolation 0-10V DC Isolated Signal Converter Signal Iaolator
<1>. GLG signal isolator provides isolated power distribution power supply for transmitter, meanwhile it isolates and converts the current signal to control room,PLC and DCS etc.
<2>. Input terminal is in common use for current source,2-wires and 3-wires. The input, output and power are isolated from each other by adopting highly efficient magnetoelectric isolation technology interiorly.
<3>. DC 24V or AC 220V power supply. Standard 35mm DIN rail independent mounting.
<4>. GLG has 6 type channels, 1 in/1 out, 1 in/2 out, 1 in/3 out, 1 in/4 out, 2 in/2 out, 2 in/4 out, input and output signal can be customized.
Power Supply | |
Power Supply | DC24V,±10% or AC85-265V |
Current Consumption |
≤50mA(1 in 1 out,24V power supply, output 20mA); |
≤70mA(1 in 2 out,24V power supply, output 20mA); | |
≤100mA(2 in 2 out,24V power supply, output 20mA); | |
Input |
|
Input Signal | 4-20mA;0-20mA;0-10mA;0-5V;0-10V;1-5V;customized |
Input Burdern | Current transformer CT≤0.2VA |
Input Impedance | ≤50Ω |
Output | |
Output Signal | 4-20mA;0-20mA;0-10mA;0-5V;0-10V;1-5V;customized |
Output Load Resistance |
RL≤500Ω(output current signal); RL≥10KΩ(output voltage signal); |
Output Ripple | ≤0.5%RO |
Other Parameters | |
Accuracy | DC;±0.1%F.S. |
Respond Time | <10ms |
Temperature Drift | 0.005%F.S./℃ (-20℃~+55℃) |
Isolation intensity | 1500V AC/1min(between input-ouput-power) |
Insulation resistance | ≥100MΩ(between input-ouput-power) |
Overload capacity | withstand double rating(continous),10 times rating(10s) |
Working Temperature & Humidity | -20℃~+55℃/<80%humidity(non condensing state) |
Storage Temperature & Humidity | -20℃~+70℃/<70%humidity(non condensing state) |