Conductor Nominal Cross-section | Conductor construction | Insulation Nominal thickness | Max.Diameter of cable | Max.d.c resistance at 20℃ | Min.Insulation resistance at 70℃ | Current rating of cable in air at 40℃ | Approx weight of cable | |||||||
mm2 | mm | mm | mm | Ω/km | mΩ.km | A | kg/km | |||||||
2*0.75 | 2*1/0.97 | 0.6 | 4.6*7.1 | 24.5 | 0.012 | 12 | 39.6 | |||||||
2*1.0 | 2*1/1.13 | 0.6 | 4.8*7.4 | 18.1 | 0.011 | 14 | 46.2 | |||||||
2*1.5 | 2*1/1.38 | 0.7 | 5.3*8.5 | 12.1 | 0.011 | 18 | 61.8 | |||||||
2*2.5 | 2*1/1.78 | 0.8 | 6.2*10.1 | 7.41 | 0.010 | 25 | 92.2 | |||||||
2*4 | 2*1/2.22 | 0.8 | 6.7*11.1 | 4.61 | 0.0085 | 33 | 125.4 | |||||||
2*4 | 2*7/0.85 | 0.8 | 6.9*11.5 | 4.61 | 0.0080 | 33 | 133.1 | |||||||
2*6 | 2*1/2.76 | 0.8 | 7.5*12.5 | 3.08 | 0.0070 | 42 | 172.6 | |||||||
2*6 | 2*7/1.04 | 0.8 | 7.8*13.0 | 3.08 | 0.0065 | 42 | 182.5 | |||||||
3*0.75 | 3*1/0.97 | 0.6 | 4.6*9.6 | 24.5 | 0.012 | 10 | 55.8 | |||||||
3*1.0 | 3*1/1.13 | 0.6 | 4.8*10.1 | 18.1 | 0.011 | 12 | 65.5 | |||||||
3*1.5 | 3*1/1.38 | 0.7 | 5.3*11.7 | 12.1 | 0.011 | 15 | 88.5 | |||||||
3*2.5 | 3*1/1.78 | 0.8 | 6.2*14.0 | 7.41 | 0.010 | 21 | 133.0 | |||||||
3*4 | 3*1/2.22 | 0.8 | 7.0*15.8 | 4.61 | 0.0085 | 28 | 197.2 | |||||||
3*4 | 3*7/0.85 | 0.8 | 7.1*16.3 | 4.61 | 0.0080 | 28 | 198.7 | |||||||
3*6 | 3*1/2.76 | 0.8 | 7.5*17.5 | 3.08 | 0.0070 | 36 | 251.8 | |||||||
3*6 | 3*7/1.04 | 0.8 | 7.8*18.2 | 3.08 | 0.0065 | 36 | 266.3 |