Product name | Intelligent Reactive Power Compensation Controller | ||
Product model | FJK-02-12F | ||
Product introduction | FJK-02 intelligent reactive power compensation controller is suitable for automatic adjustment of capacitor compensation device in low-voltage distribution system (controller for short). It enables power factor to reach user's preset state, improves utilization efficiency of power transformer, reduces line loss and improves power supply quality, thus improving economic benefits and social benefits. | ||
Functional characteristics | 1. Fully digital design, AC sampling. The human-machine interface adopts large-screen LCD and Chinese liquid crystal display. 2.Adhering to the people-oriented design concept, modular assembly and streamline design. 3. Real-time display of power factor,voltage, current, active power, reactive power, total harmonic distortion rate of voltage, total harmonic distortion rate ofcurrent, frequency, temperature, capacitance output display, switching status alarm and other information of L1, L2 and L3 phases. 4. Set Chinese prompt for parameters and enter numbers. 5. Capacitor control scheme supports three-phase compensation, split-phasecompensation and comprehensive compensation scheme. Control scheme can be set through menu. 6. It has two working modes of manualcompensation/automatic compensation. 7. The sampling physical quantity is reactive power and has harmonic measurement andprotection functions. | ||
Appearance size | Opening size: 138mm*138mm Overall dimensions: 144mm*144mm*104mm |
Product name | Reactive compensation controller |
model | FJK-02-12F |
Control the number of switching paths | 12 |
Compensation type | Hybrid compensation |
Opening size | 138*138 mm |
product wiring | Terminal description | ||||||
Terminal label | state | Explain | Remarks | ||||
Ua、Ub、Uc | input | It is three-phase sampling voltage respectively; at the same time, Ub and UC are multiplexing of working power supply of the machine | The power supply is 380V AC | ||||
Un | input | Zero line | Sampling zero line | ||||
IA、Ia、IB、Ib、IC、Ic | input | Sampling current transformer input | Respectively from three-phase La, LB and LC current transformers | ||||
COM | output | Internal 12V power output + | Connected to 12V + terminal of SCR trigger module / composite switch | ||||
K1~K12 | input | Control terminal of output from the first group to the twelfth group | Connected to 12V terminal of SCR trigger module / composite switch | ||||
A、B | communication interface | MODBUSAgreement |
Conditions of use | 1. Altitude: ≤2500m 2. Operating temperature: 65123; 30℃ ~+55℃ 3. Storage temperature: 65123; 35℃ ~+60℃ 4. No corrosive gas, no conductive dust and no inflammable and explosive medium. 5. The installation site shall be free from severe vibration and rain and snow erosion. |
Technical parameter | 1. measuring voltage: 100 v ~ 290 v 2. Measuring current: 0 ~ 6000A 3. Measuring power factor: lag 0.200 ~ lead 0.200 4. Operating power supply: 380 V 20% 5. Measurement frequency: 47 ~ 53Hz 6. Sensitivity: 50mA 7. Display active power: 0 ~ 6553 kW 8. Display reactive power: 0 ~ 6553 kVAR 9. Display voltage total harmonic distortion rate: 0.0 ~ 50.0% 10. Display current total harmonic distortion rate: 0.0 ~ 100.0% Input/output signal 1. sampling voltage: La, Lb, Lc phase voltage 2. sampling current: bus La, Lb, Lc phase current transformer secondary 0 ~ 5a 3.12V 40mA/ branch Note: The sampling voltage and sampling current must be in phase! Display performance LCD liquid crystal display data display refresh period ≤1s Communication interface data 1.Communication interface: RS-485 2. Protocol: MODBUS communication protocol 3.communication rate: 4800~38400bps (no parity bit) Measurement accuracy 1. Voltage: 0.5% 2. Current: 0.5% 3. Active power: 1.0% 4. Reactive power: 1.0% 5. Power factor: 1.0% 6. Frequency: ±0.1Hz Set data range 1. Temperature setting: 40 ~ 100 C (temperature protection value) 2. .Delay time: D1: 0.1s ~ 300sd2: 0-300s 3. . overvoltage setting: 235 v ~ 280 v 4. Switching threshold:: 0.5 ~ 1.2 (the set value is the switching threshold) Step size: 0.1 5. .Removal Threshold-1.2-Current Setting 6. current change ratio: 1 ~ 1000 (ratio value) 7. Target COSΦ φ: lag 0.85 ~ lead 1.00 8. Undervoltage setting: 175 V ~ 210 V, or off 9. Harmonic protection: HV: 0.0% ~ 100.0% (0.0% off) HI: 0.0% ~ 100.0% (0.0% off) The compensation mode and capacity of each channel of capacitor can be arbitrarily set as required.. Capacitor preset: 0 ~ 250kvar/group ID number setting This machine has communication interface and supports MODBUS protocol. This item includes ID number and communication rate setting of 485 communication interface. ID number is the address number 001 ~ 255 describing this machine in the system network. Communication rate: 4800~38400bps Reliability: mean time to failure (mtbf): > 25000 hours |