Individual feed | Single Phase for each rectifier | |
Voltage | 230 VAC/DC nominal, max 300 VAC/DC* | |
Maximum Current | 5.9 Arms for each feed* | |
Connection | 2 x 2.5mm2 for each rectifier; L + N 3 x M6 cable lug rear; PE | |
* For details see datasheet for the applicable rectifier. | ||
DC OUTPUT | ||
Voltage | 24 Vdc* | |
Maximum Current | 3 x 83 A system * | |
Connection | 6 x 16/25mm2 (3 x VDC+ and 3 x VDC-) Can be paralleled by links. | |
* For details see datasheet for the applicable rectifier. | ||
OTHER SPECIFICATIONS | ||
# rectifiers | 2 positions for each output (4 if paralleled) | |
# controller | 1 positions for each output | |
Isolation | 3.0 kVAC - input to output 1.5 kVAC - input to earth 0.5 kVDC - output to earth | |
Operating temp. | -40 to +85°C (-40 to +185°F) * | |
Storage temp. | -40 to +85°C (-40 to+185°F) | |
Mounting | Rear mounted onto a 19" frame or mounting plate (default) Front flush mounted onto a 19" frame (optional, p/n 278626) | |
MTBF | > 500, 000 hours Telcordia SR-332 Issue 1, method III (a) (Tambient: 45°C) | |
IEC Prot. Cl. | IP20 | |
Dimensions | o Height: 132.5 mm (3U) o Width: 482.6 mm (to fit into 19,,mounting) o Depth: 300 mm including rear mounting brackets, 252 mm without brackets. 300 mm depth required in enclosed cabinets for air flow | |
Weight | CS0603.000 7.8 kg (17.2 lbs) excluding modules CS0603.001 6.0 kg (13.2 lbs) excluding modules | |
* see rectifier datasheet for details on temperature derating | ||
CONTROL, MONITORING AND ALARMS | ||
Without controller Connection With Smartpack S Connection | Series connected rectifier alarm for each rectifier pair ⑴ 2 x 1.5mm2; COM, NC (To be loaded with maximum 30V and 100mA) Battery current sense ⑵ Battery and load fuse sense ⑵ 2 LVDs⑵ 10 x 1.5mm2 | |
Temp, input and alarm output connections on controller ⑵ | ||
(1) see rectifier datasheet for details (2) see Smartpack S datasheet for details | ||
APPLICABLE STANDARDS | ||
Electrical safety | IEC 60950-l/-3rdedition UL60950-l/-3rd edition | |
EMC | ETSI EN 300 386 V.l.4.1 EN 61000-6-1 (immunity, light industry) EN 61000-6-2 (immunity, industry) EN 61000-6-3 (emission, light industry) EN 61000-6-4 (emission, industry) FCC Part 15 Subpart 109 | |
Mains Harmonics | EN 61000-3-2 | |
Marine | DNV-OS-D202, Ch.2 Sec. 4 (DNV 2.4) o Temperature CL B o Humidity CL B o Vibration CL A o EMC CL B*) | |
Environment | ETSI EN 300 019-2-1 Class 1.2 ETSI EN 300 019-2-2 Class 2.3 ETSI EN 300 019-2-3 Class 3.2 ETSI EN 300 132-2 RoHS compliant | |
*)ClassAforCA0603.001 |