DC SUPPLY | Continuous Votlage Rating | 8 V to 35 V continuous |
Auto-test Commercial power | Maximum Operating Current | 100 mA at 12 V, 105 mA at 24 V |
Emergence Stop | Maxinmum Standby Current | 60 mA at 12 V, 55 mA at 24 V |
Manual Start/STOP | Maxinmum Sleep Current | 40 mA at 12 V, 35 mA at 24 V |
Long-Distance Start/Stop | Cranking Droputs | Able to survive 0 V for 50 mS, providing supply was at least |
Auto quit of Start motor | Over frequency | 10 V before dropout and supply recovers to 5 V |
Double power swicth transfer controll | Low Frequency | This is achieved without the need for internal batteries |
INPUTS | Digttal Inputs A to F | Negative switching |
Analogue Inputs D | Configurable as: | |
Negative switching digital input | ||
0 V to 10 V,4 mA to 20 mA,0 Ω to 240 Ω | ||
Analogue Inputs A TO C | Configurable as: | |
Negative switching digital input:0 Ω to 480 Ω | ||
OUTPUTS | Output A (Fuel) | 10 A short term, 5 A continuous,at supply voltage |
Output B (Start) | 10 A short term, 5 A continuous,at supply voltage | |
Auxiliary Outputs C, D, E &F | 2 A DC at supply voltage | |
GENERATOR & MAINS (UTILITY) | Voltage Range | 15 V to 415 V AC (Ph to N),26 V to 719 V AC (Ph to Ph) |
Frequency Range | 3.5 Hz to 75 Hz |