FC221-5DO | Technical Data | ||||||
Measuring values | temperature | ||||||
Output switch contact | terminal 2 | 3 – 2x 0..10 V for heating and cooling | ||||||
Output switch contact | terminal 5 | 6 | 7 – LO | ME | HI 3x normally open contact, 250 V load max. 3 A, Fan | ||||||
Network technology | RS485 Modbus, RTU, half-duplex, baud rate 4.800, 9.600, 19.200 or 38.400, parity: non (2 stopbits), even or odd (1 stopbit) | ||||||
Power supply | 24 V = (±10%) | 24 V ~ (±20%) SELV | ||||||
Power consumption | 3 W (24 V =) | ||||||
Measuring range temp. | +1..+50 °C | ||||||
Accuracy temperature | ±1 K (typ. at 21 °C) | ||||||
Inputs | terminal 10 input for external sensor NTC10K | terminal 11 – ESI | DP input digital for floating contact, window contact, dew point sensor | terminal 12 - OCC input digital for floating contact, occupancy sensor, key card switch | ||||
Control functions | set point adjustment +1..+50 °C, (default +16..+30 °C) | ||||||
Display | LCD 64x41 mm, white background lighting | ||||||
Enclosure | ABS, pure white | ||||||
Protection | IP20 according to EN 60529 | ||||||
Cable entry | rear entry | ||||||
Connection electrical | terminal block max. 1,5 mm² | ||||||
Ambient condition | -10..+50 °C, max. 95% rH non-condensing | ||||||
Weight | 160 g | ||||||
Mounting | flush mounted with standard EU box (Ø=60 mm) |