Overview and applications
·Single phase and three phase applications
·High Interruption rating capabilities.
·Overload protection
·Short circuit protection
·Positive isolation
Suitable for industrial, commercial, high-rise and civil residences circuit protection.
Type designation
Technical data
Specifications | |
Rated insulation voltage
|
500V
|
Rated impulse withstand voltage Uimp
|
4000V
|
Rated current(A)
|
6A,10A,16A,20A,25A,32A,40A,50A,63A
|
Rated frequency
|
50Hz / 60Hz
|
Number of poles
|
1P ,1P+N,2P ,3P ,3P+N,4P
|
Rated breaking capacity Icn=Ics(A)
|
6000A
|
Mechanical life(cycles)
|
≥10000
|
Electrical life(cycles)
|
≥6000
|
Tripping characteristics
|
B , C , D
|
Grid distance
|
45mm
|
Protection degree
|
IP20
|
Standard
|
IEC60898 -1,GB/T10963.1
|
Compliant certification
|
CCC
|
Table 1 Tripping characteristics(Reference temperature 30℃)
Test | Curve | Test current ln(A) | Status | Time limit for tripping or non-tripping | Expected result | Remark |
a | B,C,D | 1.13ln | Cold | t≤1h | Non-tripping | Current smoothly rises to specified value within 5s |
b | B,C,D | 1.45ln | Following item a test | t<1h | Tripping | |
c | B,C,D | 2.55ln | Cold | 1s<t<60s(ln≤32A) 1s<t<120s(ln>32A) |
Tripping | |
d | B C D |
3ln 5ln 10ln |
Cold | t≤0.1s | Non-tripping | Switch on the power supply by closing the auxiliary switch |
e | B C D |
5ln 10ln 20ln |
Cold | t<0.1s | Tripping | Switch on the power supply by closing the auxiliary switch |
Note: The term "cold " means that the test is carried out at a reference calibration temperature without load before the test.
Tripping curve
Dimensions(unit :mm)
Conductor requirements and cross-sectional area
Copper cross-sectional area(mm2) | Rated current In(A) |
1 | In≤6 |
1.5 | 6<In≤13 |
2.5 | 13<In≤20 |
4 | 20<In≤25 |
6 | 25<In≤32 |
10 | 32<In≤50 |
16 | 50<In≤63 |