Input | ||
Input signal | 4-20mA,0-20mA,0-5V,1-5V,0-10V | |
Input resistance | Impedance ≤50Ω, voltage Impedance ≥250 KΩ | |
Maximum input current / voltage | ≤30mA/≤10.5V | |
Current isolator output | ||
Output signal | 0-20mA,0-20mA,0-5V,1-5V,0-10V | |
Output load | 4-20mA, 0-20mA load resistance RL≤400Ω; 0-5V, 1-5V load resistance RL≥250KΩ, 0-10V load resistance RL≥500KΩ | |
Voltage isolator output | ||
Output signal | 0-20mA,0-20mA,0-5V,1-5V,0-10V | |
Output load | 4-20mA, 0-20mA load resistance RL≤400Ω; 0-5V, 1-5V, 0-10V load resistance RL≥20KΩ | |
Power supply | ||
Power supply | DC20-32V | |
Power consumption | Single Output Power: ≤0.8W; Dual Output Power: ≤1.0W | |
Other parameters | ||
Insulation resistance | ≥100MΩ (500VDC) | |
Dielectric strength | 2000Vrms (1 min, no spark) | |
Operating temperature | -10 ~ 50 °C (no condensation, no freezing) | |
Relative humidity | 25%~85%RH | |
Storage temperature | -10 ~ 60 °C (no condensation, no freezing) | |
Temperature drift | 0.0075%FS/℃ | |
Mounting style | 35mmDIN rail mounting | |
Dimensions | 13 * 108 * 121.2mm (W * H * D) | |
Transmission accuracy (20 °C) | 0.15%FS | |
Response time | ≤2ms | |
Weight | Approximately 130 g | |
Electromagnetic compatibility | In line with GB/T18268 industrial equipment application requirements | |
Field devices applicable | DC voltage / current source |