True double-conversion
Microprocessor control optimizes reliability
Input power factor correction
Output power factor 0.8
Wide input voltage (110 V – 300 V)
Converter mode available
ECO mode for energy saving
Generator compatible
Charger capacity expansion to 6A for long-run models
Smart SNMP works well with either USB or RS-232 together
Comprehensive display allows easy monitoring and access of UPS status
MODEL | GH11-1K (L) | GH11-2K (L) | GH11-3K (L) | |
PHASE | Single phase with ground | |||
CAPACITY | 1000 VA / 800 W | 2000 VA / 1600 W | 3000 VA / 2400 W | |
INPUT | ||||
Nominal Voltage |
100/110/115/120/127VAC or 200/208/220/230/240VAC | |||
Input Voltage Range |
55-145 VAC or 110-300 VAC | |||
Frequency Range |
40Hz ~ 70 Hz | |||
Power Factor | ≥ 0.99 @ Nominal Voltage (100% load) | |||
OUTPUT | ||||
Output Voltage |
100/110/115/120/127VAC or 200/208/220/230/240VAC | |||
Voltage Regulation |
± 1% | |||
Frequency Range (Synchronized Range) |
47~ 53 Hz or 57 ~ 63 Hz | |||
Frequency Range (Batt. Mode) |
50 Hz or 60Hz ± 0.1 Hz | |||
Current Crest Ratio | 3:1 | |||
Harmonic Distortion | ≤ 3 % THD (Linear Load) ≤ 6 % THD (Non-linear Load) |
|||
Transfer Time |
AC to DC | Zero | ||
Inverter to Bypass |
4 ms (Typical) | |||
Waveform (Batt. Mode) |
Pure Sinewave | |||
EFFICIENCY | ||||
To AC Mode | 88% | 89% | 90% | |
To Battery Mode | 83% | 87% | 88% | |
BATTERY | ||||
Standard model |
Battery type | 12V9AH | ||
Quantity | 4 | 6 | ||
Standard charging time |
4 hours charge to 90% | |||
max charge current |
1A | |||
Charging voltage | 27.3VDC±1% | 82.1VDC±1% | ||
Long-run Model |
Battery Type | Depending on the capacity of external batteries | ||
Numbers | 3 | 6 | 8 | |
Charging Current (max.) |
1.0A/2.0A/4.0A/6.0 A | |||
Charging Voltage |
41.0VDC ± 1% | 82.1 VDC ±1% | 109.4VDC ±1% | |
INDICATORS | ||||
LCD |
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
|||
ALARM | ||||
Battery Mode | Sounding every 4 seconds | |||
Low Battery | Sounding every second | |||
Overload | Sounding twice every second | |||
Fault | Continously sounding | |||
PHYSICAL | ||||
Standard models |
Dimension | 282*145*220 | 397*145*220 | 419*190*318 |
Net weight(kgs) | 9.3 | 18.6 | 30 | |
Long-run Model |
Dimension | 282*145*220 | 397*145*220 | |
Net Weight (kgs) | 4.6 | 6.8 | 7.4 |
1. OEM&ODM services acceptable.
2. 1% pcb board provided .
3. Lots of cooperated agent for shipping by sea or by air.
4. 1year warrenty , if it is quality problem , we will provide the parts for free .
Little hint:
1.In the warranty period the machine has a problem, please contact the sales staff, we will be responsible for customer service.
2.Exceed the warranty period, improper operation and man-made damage, we will still give help and support,We will provide spare parts at a cost price.
3.According to the customer's needs, we can provide unconventional, but the cost may be slightly higher than the traditional machine.
Q1: Why you should choose us?
---16 years UPS experiences
---Professional team for both oversea and domestic market
--UPS provider of SCO meeting 2015 and Shanghai-Kunming high-speed railway project
---Qualified product plus competitable prices
---Delivery in time
---Sincerely services
Q2: How is your after-sale service?
---We provide 12-24 months warranty since the delivery date and free maintenance /
replacement during warranty period.
Q3: What kind of certification you have?
---ISO9000, CE,ROHS,UL,and so on
Our products could pass different labor testing according to different countries’ requirements.
Q4: Delivery time:
---Standard products could be delivered within 15 days; customized products could be
developed within 45-60days.