Current rating range 5-30A
Input voltage rating 125/250VAC:32/50VDC
Interrupting Capacity 125/250VAC 1,000A(UL 1077)
Typical life 1,000 operations at 200% overload
Insulation co-ordination Rated impulse withstand voltage 2. 5kv
Dielectric Strength 1500VAC/min.
Insulation Resistance >100MOHM(DC 500V)
Mechanical/Environmental Data.
Operating Ambient Temperature: -10C to +60C.
Termination: 250 (6.35mm ) quick connects or solder terminals
Mounting: Various options. See Ordering Infomation and drawings
Calibration(at25℃)
100% of Rated Current: Hold, No Tnp
150% of Rated Current: Tnp Within 1 Hour.
200% of Rated Current: 5-30 sec Trip
300%0 of Rated Current: 1.5-5.0 sec Trip
Approval
Approval File No Rated current Rated voltage
CUL UL E155159 3-50A 125/250VAC:50VDC
TUV SUD B150958611007 3-30A 125/250VAC;32VDC
CCC201101030752058 3-30A 125/250VAC
VDE40036160 3-30A 125/250VACCSA102199125VAC
Sales | Tele | |
Cecilia Peng | +86-19925448720 | 19925448720 |