1. Description
FTG-12 solid insulated switchgear mainly has three functional unit modules,
namely D unit (breaker unit), I unit (load switch unit), and R unit
(fuse combination electrical unit). The main switch of each unit is a vacuum
switch.When the distribution network system requires the combination of
multiple units, it can be arbitrarily expanded according to the distribution
network requirements. Arbitrarily arrange according to different design
schemes to achieve different distribution network requirements.
2. Environmental Conditions
(1) Suitable Altitude: ≤2000mSuitable
(2) Temperature: -40℃ ~ +55℃Relative
(#) Humidity: Daily mean ≤95%, monthly mean ≤90%
(4) Gradation of Earthquake Damage: ≤ Level 8
3. Technical Parameter
D Unit | I Unit | R Unit | ||||||
Rated voltage(kv) | 12 | 24 | 12 | 24 | 12 | 24 | ||
Rated frequency (Hz) | 50 | 50 | 50 | |||||
Rated current(A) | 800 | 630 | 630 | 630 | ||||
Rated short-circuit breaking current(KA) | 25 | 20 | 20 | 31.5 | ||||
Rated cable charging breaking current(A) | / | / | 10 | 10 | ||||
Rated short-time withstand current(KA) | 25 | 20 | 20 | / | ||||
Rated short-time withstand time(S) | 4 | 4 | / | |||||
Rated peak withstand current(KA) | 63 | 50 | 50 | / | ||||
Rated short-circuit closing current (KA) | 63 | 50 | 50 | / | ||||
Rated breaking transfer current(A) | / | / | 3150 | |||||
Rated insulation level | Rated lightning impulse withstand voltage(kv) | Interphase / relatively | 75 | 125 | 75 | 125 | 75 | 125 |
Break | 85 | 145 | 85 | 145 | 85 | 145 | ||
Rated power frequency withstand voltage(kv1min) | Interphase / relatively | 42 | 65 | 42 | 65 | 42 | 65 | |
Break | 48 | 79 | 48 | 79 | 48 | 79 | ||
Auxiliary control loop | 2 | 2 | 2 | |||||
Mechanical life (times) | 10000 | 10000 | 10000 | |||||
DC resistance of main circuit (µΩ) | ≤140 | ≤140 | ≤140 |