Universal input of color paperless recorder (capable of inputting by means of configuration: standard voltage, standard current, thermocouple, thermal resistance, millivolt, etc.). It can be equipped with 18-channel alarm output or 12-channel analog transmitting output, RS232/485 communication interface, Ethernet interface, mini-printer interface, USB interface and SD card socket; can provide sensor distribution; is equipped with powerful display function, real-time curve display, historical curve retrospection, bar graph display, alarm list display, etc. The meter is of high cost effectiveness due to its humanized design, perfect function, reliable hardware quality and exquisite craft.
Input signal:
Current: 0~20mA, 0~10mA, 4~20mA, 0~10mA square root, 4~20mA square root
Voltage: 0~5V, 1~5V, 0~10V, ±5V, 0~5V square root, 1~5V square root, 0~20 mV, 0~100mV, ±20mV, ±100mV
Thermal resistance: Pt100, Cu50, Cu53, Cu100, BA1, BA2
Linear resistance: 0~400Ω
Thermocouple: B, S, K, E, T, J, R, N, F2, Wre3-25, Wre5-26
Output signal:
Analog output: 4~20mA (load resistance ≤380Ω), 0~20mA (load resistance ≤380Ω), 0~10mA (load resistance ≤760Ω), 1~5V (load resistance ≥250KΩ), 0~5V (load resistance ≥250KΩ), 0~10V (load resistance ≥500KΩ)
Alarm output: normally open relay contact output, where the contact capacity is 1 A/250 VAC (resistive load)
(! Note: Please do not carry load directly in case the load exceeds the contact capacity of relay.)
Feed output: DC24 V ± 1, load current ≤ 250 mA
Communication output: RS485/RS232 communication interface, 1,200 ~ 57,600 bps baud rate (able to be set); standard MODBUS RTU communication protocol is adopted; the communication distance of RS-485 can be as long as 1 kilometer; the communication distance of RS-232 can be as long as 15 m; EtherNet communication interface is adopted, where the communication speed is 10 M.
Product Name | pressure data logger |
Material | stainless steel |
Measurement accuracy | 0.2%FS±1d |
Sampling period | 1 s |
Setting mode | The button is set in the form of panel soft touch; setting values of parameters are locked with passwords and will be saved permanently in case of outage. |
Display method | 7-inch 800 * 480 dot-matrix widescreen TFT high brightness color graphics and LCD display; LED backlight; with clear pictures and wide visual angle. Display contents can be composed of characters, figures, conditional curves, bar graphs, etc.; through panel button, page turning, forward and backward search of historical data, time scale change of curves, etc. can be realized. |
Data backup | Data backup and conversion storage of USB flash disk and SD card are support, where the maximum capacity is 8 GB; FAT and FAT32 formats are supported. |
Storage capacity | The capacity of the internal Flash memory is 64 M Byte |
Recording interval | Nine options including 1, 2, 4, 6, 15, 30, 60, 120 and 140 s can be selected |
Storage length | 24 days (1 s interval) – 5825 days (240 s interval) |
Working power supply | AC 85 ~ 264 V (power supply of the switches), 50/60 Hz; DC12 ~ 36 V (power supply of the switches) |
power consumption | ≤20 W |
Environment condition | Environment temperature: -10 ~ 50°C; Relative humidity: 10 ~ 90% RH (without condensation of moisture); Avoidance of contact of high corrosive gas. (! Note: If the field environment is poor, special instruction should be given when ordering.) |
Input: 12 channels (universal input)
RS485 communication
Power range: AC85-265V (50/60Hz)
Ethernet communication
The above price is the price of this specification, please contact customer service if you need more changes.
A: We are factory.
A: Generally it is 5-10 days if the goods are in stock. or it is 15-20 days if the goods are not in stock, it is according to quantity.
A: Yes, we could offer the sample for free charge but do not pay the cost of freight.
A: Payment<=1000USD, 100% in advance. Payment>=1000USD, 30% T/T in advance ,balance before shippment.
If you have another question, pls feel free to contact us as below: