Feature |
1. 100% unbalance loads design.
2. Low frequency, pure sine wave output.
3. Wide AC voltage input range, AVR output.
4. Peak power more than 3 times.
5. LCD display for all working datas.
6. AC prior/EC mode/Battery prior selectable.
7. AC charge current 0~45A selectable.
8. Seven battery type selectable.
9. 50Hz/60Hz automatic recognition.
10. Support diesel/gasoline generator input.
11. RS232/RS485/APP/SNMP/GSM communication port optional.
Details |
Parameters |
Specification | |||||||
Model HDSX | 10348 | 10396 | 103192 | 15396 | 153192 | 153384 | |
Rated Power | 10KW | 10KW | 10KW | 15KW | 15KW | 15KW | |
Battery Voltage | 96VDC | 192VDC | 384VDC | 96VDC | 192VDC | 384VDC | |
N.W.(kg) | 110 | 110 | 110 | 145 | 145 | 145 | |
G.W.(kg) | 128 | 128 | 128 | 163 | 163 | 163 | |
Size(L*W*Hmm) | 725*365*1010 | ||||||
Packing Size(L*W*Hmm) | 785*425*1135 | ||||||
Parameter | |||||||
Input | Battery Input Voltage Range | 42V~60V for 48V system; 84V~120V for 96V system; 168V~240V for 192V system; 336V~480V for 384V system | |||||
AC Input Voltage Range | 380Vac/400Vac±10%(customized 190Vac/200Vac) | ||||||
AC Input Frequency Range | 45Hz-65Hz | ||||||
Phase | 3/N/PE | ||||||
Output | Efficiency(Battery Mode) | ≥85% | |||||
Output Voltage(Battery Mode) | 380Vac/400Vac±10%(customized 190Vac/200Vac) | ||||||
Output Frequency(Battery Mode) | 50/60Hz ±1% | ||||||
Output Wave(Battery Mode) | Pure Sine Wave | ||||||
Output waveform distortion | Linear load≤3% | ||||||
Efficiency(AC Mode) | >99% | ||||||
Output Voltage(AC Mode) | Conforming to AC input | ||||||
Output Frequency(AC Mode) | Conforming to AC input | ||||||
Phase | 3/N/PE | ||||||
AC charger | AC charging current | 0~45A selectable | |||||
AC charging method | Three-stage(constant current, constant voltage, floating charge) | ||||||
Battery type (Optional) | U0: Gel U.S.A | Charge Voltage: 56V for 48V system, 112V for 96V system, 224V for 192V system, 448V for 384V system; Float Voltage: 54.8V for 48V system, 109.6V for 96V system, 219.2V for 192V system, 438.4V for 384V system. | |||||
U1: A.G.M.1 | Charge Voltage: 56.4V for 48V system, 112.8V for 96V system, 225.6V for 192V system, 451.2V for 384V system; Float Voltage: 53.6V for 48V system, 107.2V for 96V system, 214.4V for 192V system, 428.8V for 384V system. | ||||||
U2: A.G.M.2 | Charge Voltage: 58.4V for 48V system, 116.8V for 96V system, 233.6V for 192V system, 467.2V for 384V system; Float Voltage: 54.8V for 48V system, 109.6V for 96V system, 219.2V for 192V system, 438.4V for 384V system. | ||||||
U3: Sealed lead Acid | Charge Voltage: 57.6V for 48V system, 115.2V for 96V system, 230.4V for 192V system, 460.8V for 384V system; Float Voltage: 54.4V for 48V system, 108.8V for 96V system, 217.6V for 192V system, 435.2V for 384V system. | ||||||
U4: Gel European | Charge Voltage: 57.6V for 48V system, 115.2V for 96V system, 230.4V for 192V system, 460.8V for 384V system; Float Voltage: 55.2V for 48V system, 110.4V for 96V system, 220.8V for 192V system, 441.6V for 384V system. | ||||||
U5: Open lead Acid | Charge Voltage: 59.2V for 48V system, 118.4V for 96V system, 236.8V for 192V system, 477.2V for 384V system; Float Voltage: 54V for 48V system, 108V for 96V system, 216V for 192V system, 432V for 384V system. | ||||||
U6: Calcuim(open) | Charge Voltage: 60.4V for 48V system, 120.8V for 96V system, 241.6V for 192V system, 483.2V for 384V system; Float Voltage: 54.4V for 48V system, 108.8V for 96V system, 217.6V for 192V system, 435.2V for 384V system. | ||||||
U7: Sulphation cycle | 15.5V for 4hrs | ||||||
customize battery | Charge and discharge parameters of different types of batteries (such as lithium batteries, etc.) can be customized according to user requirements. | ||||||
Working Mode(Selectable) | AC prior(d1) | Under AC prior mode, device will always use utility source and through regulator to supply loads as well as charge battery(charging current selectable); when utility power is with high/low/serious distortion or other abnormal, device will auto converter battery source to supply loads. | |||||
EC mode(d2) | Under Energy saving mode, device dedects load, when the load is <10% rated power, device will auto on/off AC output; when the load is > 10% rated power, device will start AC output. | ||||||
Battery prior(d3) | Under Battery prior mode, device will always use battery source to coverter high quality electricity for load; when battery source is failed, device will auto use utility source and through regulator to supply loads. | ||||||
Protection | Battery low voltage alarm | 44V for 48V system, 88V for 96V system, 176V for 192V system, 352V for 384V system | |||||
Battery low voltage protection | 42V for 48V system, 84V for 96V system, 168V for 192V system, 336V for 384V system | ||||||
Battery high voltage alarm | 60V for 48V system, 120V for 96V system, 240V for 192V system, 480V for 384V system | ||||||
Battery high voltage protection | 68V for 48V system, 136V for 96V system, 272V for 192V system, 544V for 384V system | ||||||
Battery high voltage recover | 58V for 48V system, 116V for 96V system, 232V for 192V system, 464V for 384V system | ||||||
Overload protection | Automatic protection (battery mode), circuit breaker or insurance (AC mode) | ||||||
Inverter output short circuit protection | Automatic protection (battery mode), circuit breaker or insurance (AC mode) | ||||||
Temperature protection | >90°C(Shut down output) | ||||||
Alarm | A | Normal working condition, buzzer has no alarm sound | |||||
B | Buzzer sounds 4 times per second when battery failure, voltage abnormality, overload protection | ||||||
C | When the machine is turned on for the first time, the buzzer will prompt 5 when the machine is normal | ||||||
Transfer Time | ≤4ms | ||||||
Display | LCD | ||||||
Thermal method | Cooling fan in intelligent control | ||||||
Communication | RS232/RS485/APP/SNMP/GSM(Optional) | ||||||
Environment | Operating temperature | -10℃~40℃ | |||||
Storage temperature | -15℃~60℃ | ||||||
Noise | 2000m(More than derating) | ||||||
Elevation | ≤65dB | ||||||
Humidity | 0%~95% ,No condensation | ||||||
Note: All specifications are subject to change without prior notice |
Wiring Diagram |
1. Battery number and capacity should be configured according to the rated voltage of the solar power system or invertor;
2. We offer 3 optional working modes (transfer time≤4ms):
01 Grid priority mode: When the grid and battery are connected to the invertor, grid will supply power to the loads directly after voltage being stabilized and charge batteries via invertor. When the grid is cut off, the battery will automatically continue to supply power via invertor.
02 Energy saving mode: If the power of the connected AC loads is lower than 5% of the invertor’s rated power, there will be no output from the invertor. Only the chip of invertor is working. The power consumption of the invertor is only 1~6W. The LCD shows the output voltage 0. If the power of the connected loads is over 5%, within 5S the invertor will automatically convert DC to AC to supply power for the loads . The LCD shows the output voltage.
03 Battery priority mode: When the grid and battery are connected to the invertor, battery will supply power to the loads first. When battery capacity is not enough, the grid will continue to supply power automatically.
100% Testing |
Our customers are here all over the world
OUR GURANTEE & SERVICE
1. Battery gurantee period: 12 months.
2. Professional guide for your requirment.
3. The same before & after sale service: profesional and dedicated.
4. Offer you the competive price.
5. Goods delivery always be on time.
6. We insist in people-oriented, your satisfy is the power for us.
7. 100% QC inspection and testing before shipment.
8. If failure occurs under normal usage within warranty period, Xindun Power will provide free maintenance based on the proof-documents.
9. If failure or damage occurs due to incorrect operation, wire connection, or any other mis-opeartions, Xindun Power will provide pay maintenance on charge basis.
Q1: Are you a factory?
A1: Yes, we are a factory specialized in inverter field over 11 years, solar controller and solar generator since 2005 year.
Q2: Are you inverter pure sine wave output?
A2: Yes, all of our inverters are pure sine wave output.
Q3: What kind of output you can do?
A3: Normally, we produce inverter with 110v/ 50Hz, 120V/ 60Hz, 220v/ 50Hz, 230v/ 50Hz, 240V/50Hz.
If you have special requirements, pls tell us for engineer consulting.
Q4: What appliances your inverters can load?
A4: Our inverter can load household appliances other inductive load such as refrigerator, air condition, water pump, etc.
Q5: Why choose us?
A5: 1. Provide the long time maintenance service.
2. Provide the extended warranty as expected.
3. Provide the regular routine maintenance service.
4. 100% QC inspection and testing before shipment.
5. CE listed, competitive price.
6. OEM/ODM Acceptable.
7. China Telecom's Considered Cooperation Partner.