Power(kW) | Voltage(kV) | Frequency(Hz) | Size(mm,L*W*H) | Weight(Kg) |
100 | 400 | 50 | 1100*900*1000 | 320 |
200 | 400 | 50 | 1350*1100*1100 | 450 |
300 | 400 | 50 | 1500*1200*1200 | 650 |
400 | 400 | 50 | 1700*1500*1500 | 830 |
500 | 400 | 50 | 1700*1600*1600 | 950 |
600 | 400 | 50 | 1800*1600*1600 | 1150 |
800 | 400 | 50 | 1900*1800*1700 | 1900 |
1000 | 400 | 50 | 2300*1700*2100 | 2100 |
1200 | 400 | 50 | 2500*1800*2200 | 2300 |
1500 | 400 | 50 | 2500*1860*2300 | 2600 |
Model | RATA-R800kW/400V-50Hz pf1.0 |
Formation | One load bank(Including dry resistance load 800KW, electrical control components, measurement and control system) |
Power | 800kW |
Three phase resistive load grading 2500W | 1kW、2kW、2kW、5kW、10kW、10kW、20kW、50kW、100kW、100kW、 100kW、100kW、100kW、100kW、100kW |
Load connection | Star connection |
Resistance tube | Each resistance element: insulation impedance DC1000V/100MΩ above Withstand voltage ac 2000v for 5min Resistance error of each resistance tube:plus or minus 3 percent |
Load character | Resistive load |
Load control | Manual button control |
Loading accuracy | Less than or equal to 3 percent |
Three phase balance | Unbalance degree less than or equal to 3 percent |
Regulatory capacity | Minimum step 1kW |
Way of working | Continuous work |
External working power supply | TN-C,380V/50Hz |
Environment temperature | 15 degrees centigrade below zero to 55 degrees centigrade |
Cooling mode | Forced air cooling,side exhaust |
Insulation class | Class F |
Measurement accuracy | The display accuracy is 0.5,the sampling accuracy is 0.2 |
Electrical parameter display | Three phase voltage, three-phase current, frequency, power and other electrical parameters |
Load protection | Short circuit, over current, high temperature, fan fault protection |
Reference weight | 1800Kg |
Use occasion | Indoor |