Specifications |
||
Input |
Rated Voltage |
Single phase220V, three phase 200V, three phase 380V, three phase 480V; 50Hz/60Hz |
Range |
Voltage: ±20% voltage unbalance rate:<3%; frequency: ±5% |
|
Output |
Rated voltage |
0~200V/220V/380V/480V |
Frequency range |
0Hz~500Hz |
|
Frequency resolution |
0.01Hz |
|
Overload ability |
150% rated current for1minute, 180% rated current for3 seconds |
|
Control function
Control function |
Modulation modes |
Optimized space voltage vector SVPWM modulation |
Control mode |
Sensorless vector control (with optimal low frequency compensation) |
|
Frequency precision |
Digital setting: The highest frequency×± 0.01% Analog setting: The highest frequency ×±0.2% |
|
Frequency resolution |
Digital setting: 0.01Hz; Analog setting: The highest frequency× 0.1% |
|
Start frequency |
0.40Hz~20.00Hz |
|
Torque boost |
Auto torque boost, manual torque boost 0.1%~30.0% |
|
V/F curve |
Five ways: constant torque V/F curve, 1 kind of user defined V/F curve ,3 kinds of down torque curve(2.0/1.7/1.2times the power) |
|
Acc./Dec. curve |
Two ways: linear Acc./Dec., S-curve Acc./Dec.;7 kinds of Acc./Dec. time, Time unit (minute/second) optional, max. Time: 6000 mins. |
|
DC braking |
DC braking start frequency:0~15.00Hz braking time:0~60.0s braking current:0~80% |
|
Energy consuming braking |
Below 22KW drive built-in energy consuming braking unit, external braking resistor is optional. |
|
Jog running |
Jog frequency range:0.1Hz~50.00Hz, JOG Acc./Dec. time: 0.1~60.0s |
|
PID built-in |
Easily constitute a close loop control system |
|
Multi-stage speed running |
Multi-stage speed running available through built-in PLC or control terminals |
|
Textile swing frequency |
Swing frequency available with preset and center frequency adjustable |
|
Auto voltage regulation |
Keep a stable voltage automatically when the grid voltage transients |
|
Auto energy saving running |
Saving energy by auto optimizing V/F curve according to the load |
|
Auto current limiting |
Auto current limiting to prevent frequent over current fault trip |
|
Fixed-length control |
Inverter stops when reaches the preset length |
|
Communication |
RS485 standard communication port available, support MODBUS communication protocol of ASCII and RTU, master-slave multi-machine interaction function available |
|
Control panel |
LED digital display |
Display setting frequency, output voltage, output current, etc. |
External meter display |
Display output frequency, output current, output voltage, etc. |
|
Key lock |
All the keys can be locked |
|
Parameter copy |
Function code parameters are able to be copied between inverters when use remote control panel. |
|
Protection function |
Overcurrent protection; overvoltage protection; undervoltage protection; overheating protection; overload protection, etc. |
|
Environment |
Environment |
Indoors, free from direct sunlight, dust, corrosive gas, oil mist, steam, water dropper salt, etc. |
Altitude |
Lower than 1000m (derating is necessary above 1000m) |
|
Ambient temperature |
-10℃~+40℃ |
|
Humidity |
<90%RH, no condensation |
|
Vibration |
Lower than 5.9m/s (0.6g) |
|
Storage temperature |
-20℃~+60℃ |
|
Structure |
Protection level |
IP20(In the selection of state display unit or the keyboard state) |
Cooling |
Forced air cooling |
|
Installation |
Wall mounted; Floor mounted |